User Guide

Figure 1
Testing & Code Compliance
UL LISTE D
Motor..............................................................................1/4 HP ,120VAC, 60HZ
Incandescent....................................................................800W-120VAC, 60HZ
Operating Temperature ...................................................32°to 131°F (0°to 55°C)
Adjustable Light Level ................................................................10FC—150FC
Adjustable Time Delay ................................................................15 sec.-30min
Sensitivity Adjustment.........................................50% or 100% (DIP switch 1)
Coverage……………………...................……………………………Up to 1200 ft
2
Fluorescent ...................................800VA-120VAC / 1600VA-277VAC, 60HZ
Resistive ..........................................................................800W-120VAC, 60HZ
The MPC-50V provides a 360° coverage pattern, up to 1200 square feet. The
coverage shown represents walking motion at a mounting height of 8 feet(See
Figure 1 ).For building spaces with lower levels of activity or with obstacles
and barriers, coverage size may decrease.
44 ft
13.4m
8 ft
22 ft 22 ft13 ft 13 ft7 ft 7 ft3 ft 0 3 ft
Typical
desk-top
level
Coverage Pattern
Description: The MPC-50V 360 °passive infrared (PIR) occupancy sensors turn lighting systems
on and off based on occupancy and ambient light levels. The light level feature keeps lights from
turning on if the ambient light level is sufficient. The sensors can be configured to turn lighting on,
and hold it on as long as the sensor detects occupancy. After no movement is detected for a
specified time the lights are switched off.
360° Passive Infrared
L
ine Voltage Occupancy Sensor
Model #: MPC-50V
General
Specification
Passive Infrared
Technology(PIR)
360 ° field of view, 1200sqft
Time Delay is adjustable
from 5 seconds to 30
minutes
Simple, fast installation
Adjustable sensitivity
settings
Light level is adjustable.
Specifications
Features

Summary of content (4 pages)