User manual

6 www.enersys.com
Publication No: US-NP-AM-003 January 2011
Range Summary
TERMINAL
LAYOUT
Charging
Standby use: Apply constant voltage charging at 2.275 volts
per cell (or 2.25–2.30VPC).
Cyclic use: Apply constant voltage charging at 2.40-2.50 VPC.
Initial charging current should be set at less than 0.25CA.
Top charge: Product in storage (ambient temperature 25°C/77°F)
requires a top charge every six months. Apply constant voltage at
2.40 volts per cell, initial charging current should be set at
less than 0.1CA for 15 to 20 hours.
Discharge
Stop operation when voltage has reached the minimum
permissible voltage. Recharge immediately.
Do not operate above 6CA or more current continuously.
Storage
Always store battery in a fully charged condition.
If battery is to be stored for a long period, apply a recovery
top-charge every 6 months.
Store batteries in a dry and cool location.
Temperature
Keep within ambient temperatures of –15
0
C to +50
0
C for both
charging and discharging.
Incorporating battery into equipment
Install battery in a well ventilated compartment.
Avoid installing battery near heated units such as a transformer.
House the battery in the lowest section of the equipment
enclosure or rack to prevent unnecessary battery temperature
rise.
Others
Avoid terminal short circuit.
Avoid exposure of the ABS container and cover material to PVC-based
rubber mats or spacers
DO NOT expose to open flame
.
WARNING - Avoid exposure of the battery to any type of
oil, solvent, detergent, petroleum-based solvent or ammonia
solution. These materials could potentially cause permanent
damage to the battery jar and cover and will void the warranty.
Maximum Permissable Current (Amps)
Terminal Continuous 1Hr. 1 Min.
Faston tab 187 16 24 48
Faston tab 250 25 38 75
Wire Lead 0.5mm^2 7 20 30
All Bolt or Receptacle 6CA
INCH = MM INCH = MM
INCH = MM
INCH = MM
Faston Tab: 187
Faston Tab: 187
Faston Tab: 250
M5 Bolt Fastened Terminal
M5Threaded Receptacle
M6 Bolt Fastened Terminal
M6 Threaded Receptacle
JST No. VHR-2N
Tyco. 1-480318-0
M8 Bolt Fastened Terminal
M10 Bolt Fastened Terminal
“Camcorder” Terminal
M8 “Universal” Bolt Fastened Terminal
INCH = MM
INCH = MM
INCH = MM
INCH = MM
INCH = MM
INCH = MM
INCH = MM
54153_US_NP_AM_003.qxp:NP AppManual 1/21/11 1:45 PM Page 6