User manual
6 www.enersys.com
Publication No: US-NP-AM-003 • January 2011
Range Summary
• TERMINAL
• LAYOUT
Charging
•
Standby use: Apply constant voltage charging at 2.275 volts
per cell (or 2.25–2.30VPC).
•
Cyclic use: Apply constant voltage charging at 2.40-2.50 VPC.
Initial charging current should be set at less than 0.25CA.
•
Top charge: Product in storage (ambient temperature 25°C/77°F)
requires a top charge every six months. Apply constant voltage at
2.40 volts per cell, initial charging current should be set at
less than 0.1CA for 15 to 20 hours.
Discharge
•
Stop operation when voltage has reached the minimum
permissible voltage. Recharge immediately.
•
Do not operate above 6CA or more current continuously.
Storage
•
Always store battery in a fully charged condition.
•
If battery is to be stored for a long period, apply a recovery
top-charge every 6 months.
•
Store batteries in a dry and cool location.
Temperature
•
Keep within ambient temperatures of –15
0
C to +50
0
C for both
charging and discharging.
Incorporating battery into equipment
•
Install battery in a well ventilated compartment.
•
Avoid installing battery near heated units such as a transformer.
•
House the battery in the lowest section of the equipment
enclosure or rack to prevent unnecessary battery temperature
rise.
Others
•
Avoid terminal short circuit.
•
Avoid exposure of the ABS container and cover material to PVC-based
rubber mats or spacers
•
DO NOT expose to open flame
.
•
WARNING - Avoid exposure of the battery to any type of
oil, solvent, detergent, petroleum-based solvent or ammonia
solution. These materials could potentially cause permanent
damage to the battery jar and cover and will void the warranty.
Maximum Permissable Current (Amps)
Terminal Continuous 1Hr. 1 Min.
Faston tab 187 16 24 48
Faston tab 250 25 38 75
Wire Lead 0.5mm^2 7 20 30
All Bolt or Receptacle 6CA
INCH = MM INCH = MM
INCH = MM
INCH = MM
Faston Tab: 187
Faston Tab: 187
Faston Tab: 250
M5 Bolt Fastened Terminal
M5Threaded Receptacle
M6 Bolt Fastened Terminal
M6 Threaded Receptacle
JST No. VHR-2N
Tyco. 1-480318-0
M8 Bolt Fastened Terminal
M10 Bolt Fastened Terminal
“Camcorder” Terminal
M8 “Universal” Bolt Fastened Terminal
INCH = MM
INCH = MM
INCH = MM
INCH = MM
INCH = MM
INCH = MM
INCH = MM
54153_US_NP_AM_003.qxp:NP AppManual 1/21/11 1:45 PM Page 6