Installation & Operating Manual 3001391 06.14 GSV 200-450 Grease Fan USA CAN Product Information ........................ Chapter 1 + 2 Mechanical Installation ......................... Chapter 3 Electrical Installation ............................. Chapter 4 Start Up and Configuration .................. Chapter 5 Maintenance and Troubleshooting ...... Chapter 6 Job Name: Installer: Installation Date: EXHAUSTO Inc. 1200 Northmeadow Pkwy. Suite 180 Roswell, GA 30076 P: 770.587.3238 F: 770.587.
3001391 06.14 1. Product Information 2. Specifications 3. Mechanical Installation 4. Electrical Installation 5. Start-up & Configuration 1.1 1.2 1.3 1.4 Function...................................................................................................... 4 Components................................................................................................ 4 Shipping...................................................................................................... 5 Warranty..........
001391 06.14 Symbol Legend: The following terms are used throughout this manual to bring attention to the presence of potential hazards or to important information concerning the product. Danger: Indicates an imminently hazardous situation which, if not avoided, will result in death, serious injury or substantial property damage. Caution: Indicates an imminently hazardous situation which, if not avoided, may result in personal injury or property damage.
3001391 06.14 1. Product Information 1.1 Function Use ENERVEX Model GSV Grease Fan is designed to provide a large exhaust volume at a high discharge velocity. It is intended for use as a part of a restaurant kitchen exhaust system and grease applications according to NFPA 96.The use of the ENERVEX Grease Fan is not restricted to any type of chimney or grease duct. However, always follow the exhaust-hood manufacturer’s instructions regarding the venting.
3001391 06.14 1.3 Shipping Protection The fan is shipped in a corrugated cardboard box. If a transport securing device is attached (GSV 400 and GSV 450 only) to the bottom of the fan to hold the motor and impeller in place, do not remove it when unpacking the fan. ! Do not remove the transport securing device until the fan is being installed on the duct or the roof curb. The motor shaft could be damaged.
3001391 06.14 3. Mechanical Installation 3.1 Positioning In accordance with NFPA 96, roof mounted fans shall have their discharge outlet at least 40 inches above the roof surface. 3.2 Installation on Steel Duct • Insert the adapter (FR) into the grease duct, where the long collar engagement ensures safe anchoring (See Fig. 2). If necessary, the adapter can be secured by means of long self-tapping stainless steel screws into the side of the collar through the chimney wall.
3001391 06.14 3.4 Termination of Venting System In order to achieve optimal performance and energy consumption for the RS Fan or GSV Fan, the duct must be installed as shown below and the distances observed. From the last elbow to the termination point the distance has to be 3 times the diameter of the flue. For example if you using 12in flue (12 X 3 = 36in). So the distance from the last elbow to the fan termination point should be 36 inches. 3.
3001391 06.14 4. Electrical Installation 4.1 Electrical Requirements Power requirements depend on the fan size. They can be found on page 4. ! ! Danger: Turn off electrical power before servicing. Contact with live electric components can cause shock or death. Notice: If any of the original wire supplied with the system must be replaced, use similar wire of the same temperature rating. Otherwise, insulation may melt or degrade, exposing bare wire. 4.
3001391 06.14 4.3 Wiring Diagram for GSV 400-450 The connection diagram below shows how the fan is connected to the power source (see Fig. 7). Use a 3-conductor wire of min. 14 AWG with ground. Wiring must be run outside the duct, but can run between the duct and the roof curb. If variable speed is required, a variable frequency drive (VFD) can be used. This will eliminate the need for a magnetic starter as shown.
3001391 06.14 4.4 Dual Voltage Motor Wiring GSV 400-450 can operate at either 3x208-230 VAC (default) or 3x440-480 VAC. The motor wiring terminals in Fig. 8 show default jumper positions for 3x208-230 VAC operation. If the application requires 3x440-480 VAC operation, the jumper positions must be changed according to Fig. 9. Fig. 8 Fig. 9 After wiring, make sure the motor is rotating in the proper direction. This is marked on the motor end cover.
3001391 06.14 5. Start-up and Configuration 5.1 System Testing • Check the voltage with the motor nameplate rating. • Check that the transport securing device holding the motor shaft and impeller in place has been removed. • • Determine if the impeller is free and has not been subject to misalignment in shipping or installation. Apply power and check that the impeller is rotating in the direction of the arrow on the side of the top motor cover.
3001391 06.14 6. Maintenance and Troubleshooting 6.1 Maintenance Intervals The ENERVEX Grease Fan is designed for prolonged use. For dirty or grease-laden exhaust, inspect the impeller after (3) months and set up a periodic inspection based on these findings. Clean as required. The fan motors are equipped with permanently lubricated sealed ball bearings. They require no lubrication. 6.
3001391 06.14 6.