Letter Min. clearances Description
A 12’’ (30 cm) Clearances above grade level or any adjacent surface that might support snow, ice, or debris
B 39’’ (100 cm) Clearance to window or door that may be opened
F 39’’ (100 cm) Clearance to corner or adjacent wall
H 39’’ (100 cm)
Not to be installed above a meter/regulator assembly within 39" (100 cm) horizontally from the
vertical center-line of the regulator and for 15’ vertically
I 72’’ (183 cm)
Clearance to gas service regulator vent outlet or within 39’’ (100 cm) of an oil tank vent or an oil
tank fill inlet
J 39’’ (100 cm) Clearance to the combustion air inlet to any other appliance
K 72’’ (183 cm) Clearance to a mechanical air supply inlet
L 84’’ (213 cm) Clearance above paved side-walk or a paved driveway located on public property
39’’ (100 cm) Clearance to property boundary
A vent shall not terminate underneath a veranda, porch, or deck
United States:
Not Less than 36’’ (91 cm) above any forced air inlet located within 10 feet (305 cm);
Not Less than 48’’ (122 cm) below and horizontally from, or one foot (30 cm) above, any door, window or gravity air inlet into any
building;
Not Less than 24’’ (61 cm) from an adjacent building and not less than 84’’ (213 cm) above grade when located adjacent to a public
walkway.
Cannot be located less than 12 inches (300mm) above grade.
Cannot be located above a gas meter/regulator within 3 feet (900mm) horizontally of the vertical center line of the regulator.
Not within 6 feet (1.8 meters) of a gas service regulator vent outlet.
Other restrictions may apply. See NFPA 211 for further information.