Owner`s manual

United States:
Not Less than 36’’ (91 cm) above any forced air inlet located within 10 feet (305 cm);
Not Less than 48’’ (122 cm) below and horizontally from, or one foot (30 cm) above, any door, window
or gravity air inlet into any building;
Not Less than 24’’ (61 cm) from an adjacent building and not less than 84’’ (213 cm) above grade when
located adjacent to a public walkway.
Cannot be located less than 12 inches (300mm) above grade.
Cannot be located above a gas meter/regulator within 3 feet (900mm) horizontally of the vertical center
line of the regulator.
Not within 6 feet (1.8 meters) of a gas service regulator vent outlet.
Other restrictions may apply. See NFPA 211 for further information.
a) Vertically with new chimney system
(Refer to Figure 13)
NOTE: Follow vent chimney manufacturer’s instructions.
OPTION: To achieve a centered vertical installation, a 45º elbow and a clean-out tee can be used to offset
the pipe from the exhaust outlet to the rear center of the stove.
OPTION: Install vent elbow in place of clean-out tee. Locate stove. Drop plumb bob to center of tee outlet,
mark point on ceiling. Install ceiling support and vent pipe per vent manufacturer’s instructions.
1. Always maintain 3” clearance from combustible materials. When passing through additional floors or
ceilings, always install firestop spacer.
2. After lining up for hole in roof, cut either a round or square hole in roof, always 3” larger all the way
around pipe. Install upper edge and sides of flashing under roofing materials, nail to the roof along
upper edge. Do not nail lower edge. Seal nail heads with flexible waterproof sealant.
3. Apply flexible, waterproof sealant where the storm collar meets the vent. Slide storm collar down until it
sits on the flashing. Seal and install cap. Mobile home installations must use a spark arrester.