Owner`s manual

c) Vertically into existing chimney system
(Refer to Figure 14)
As an alternative, 4” vent can be run inside existing chimney to termination (Figure 14). This is the preferred
method.
Follow guidelines for equivalent vent length.
d)
V
ertically into existing masonry fireplace
(Refer to figure 15)
NOTE: Follow vent chimney manufacturer’s
instructions.
1. Have the masonry chimney inspected by a
qualified chimney sweep or installer to
determine its structural condition.
2. You will need a pipe length equal to the
chimney height from the hearth. If outside
combustion air is to be used, you will need a
pipe length equal to the chimney height plus 18
inches.
3. Install a blanking plate and the chimney pipe,
and if used the outside air pipe, as shown in
Figure 15.
4. Attach the adapter, a section of pipe and clean
out tee, making sure the clean out tee is
centered in the chimney flue area. Use RTV,
metallic tape, and a minimum of three self-
taping screws at all joint connections to ensure a
tight seal.
5. Position the stove, adhering to the clearances in
Figures 1, 2, 3 & 4.
6. Measure and build chimney top plate. Cut out holes for chimney pipe, and if used the outside air pipe.
Install and seal with non-hardening mastic to prevent water leakage. Install vent cap.
Figure 15
Venting through masonry
chimney
FIGURE 14
Venting through
existin
g
chimne
y