Installation Manual RINS1903-1 EN50131-1:2006+A1:2009 EN50131-3:2009 EN50131-6:2008 EN50131-5-3:2005+A1:2008 PD6662:2010+IA:2015 Software Version >10 PIEZO WARNING The Enforcer system contains a 100dBA siren, please be aware of this after an activation Enforcer Time 10:09 c
CONTENTS PAGE 1. Introduction ............................................................................................................................3 1.1 System Overview.................................................................................................................3 2. Specification and Warranty ........................................................................................................4 2.1 Technical Specification...........................................................
Enforcer: Installation Manual 1. Introduction The Enforcer is a wireless alarm system that has been designed to enable easy installation and minimal maintenance. The Enforcer protects the property (domestic or commercial) with a multitude of unique features: • Two Way Wireless Protection • Signal Strength Indicator (SSI) • Instant Two Way Device Control • Pyronix High Security Wireless Protocol Encryption • Programmable Wireless Supervision Time • Intelligent Wireless Jamming Detection 1.
Enforcer: Installation Manual 2. Specification and Warranty 2.1 Technical Specification Enforcer Mains Inputs European rated voltage 230V AC -15/+10% European rated current 83mA Capable operating voltage 90 - 264V AC Current 222mA - 75mA Rated Frequency 50 / 60Hz Input Fuse Rating T 2A (cannot replace) PSU Type A Radio Frequency 868MHz, FM Transceiver Narrow Band Enforcer Battery Output instant voltage 12.
Enforcer: Installation Manual 3. Installation Guide NOTE 1: It is recommended that the Engineer menu is accessed prior to opening a powered Enforcer. NOTE 2: If any new peripheral is installed (i.e. Modem, I/O board, Expander) it is recommended that the Enforcer is powered down (mains and battery). 1. Slightly unscrew the two screws located at the bottom. NOTE: Do not fully unscrew at these can be used as a 'hanger' to the rear casing as shown in Step 3. 2.
Enforcer: Installation Manual 3.2 Inside of the Enforcer: Rear 1. Terminals for Earth and Mains Supply. 2. If a modem is required (DIGI-PSTN, DIGIPSTN/VOICE, DIGI-GPRS, DIGI-LAN or DIGI-WIFI) then this space is used to install them. 3. The transformer is situated in a housing. 4. The rear tamper adjustment screw is used if the tamper from the front of the Enforcer isn't sitting flush to the back plate - this may happen if the Enforcer is installed on an uneven surface. 5.
Enforcer: Installation Manual 3.4 Connecting / Replacing the Control Panel Battery 1. Unscrew the battery compartment 2. Connect the battery pack 3. Close the battery compartment masking sure no battery cable is trapped underneath. NOTE: The Enforcer back up battery must be replaced by the manufacturer’s recommendation. The part code for this battery is BATT9V6/2Ah1-WE. The battery is NiMH 8 cell 2200mAh rechargeable.
Enforcer: Installation Manual 3.6 RS232 Connection / Uploading and Downloading Software The Enforcer PC software (InSite) can be downloaded from http://www.pyronix.com/pyronixdownloads.php. To enable the Enforcer to receive upload/download commands, refer to the function ‘SET UP DOWNLOAD’ in the programming manual. Serial Connection (RS232) 1. 2. 3. 4. 5. 6. 7. Open up InSite. Click on Roving Dial Customer. Enter the panels’ Engineer code. Enter the site name.
Enforcer: Installation Manual 3.7 Input / Output Board The Input/output (I/O) board contains the RS485 terminals that are used to connect additional wired keypads, readers, input expanders and output expanders .
Enforcer: Installation Manual Connecting Internal Tag Readers (EUR-107) Up to 3 readers can be connected to the Enforcer. Each keypad or reader need to be addressed as described below. These will also need assigning in the Engineer function '‘Assign Keypads / Readers’. Addressing at the Reader Address 1 = SWITCH 1 ON. Address 2 = SWITCH 2 ON. Address 3 = SWITCH 1: ON, SWITCH 2: ON.
Enforcer: Installation Manual Wiring a Wired External Sounder To create the bell tamper circuit, a resistor is required across 0V supply and tamper circuit of the bell box. Note that the input must be programmed as ‘tamper’. The resistor value will correspond to the value selected in ‘WIRING CHOICE’. IMPORTANT: THE BELL BOX CONNECTED WILL NEED TO BE IN SCB MODE. Unless the bell box is a Pyronix Deltabell. Wiring Wired Inputs The End of Line value for all wired inputs is programmed in ‘CHOOSE MODE’.
Enforcer: Installation Manual 3.9 Connecting a Wired Input Expander Up to 4 x Remote Input Expanders can be connected to the Enforcer. NOTE: The above shows the I/O board connected to a EURO-ZEM8+, the connections for a EUROZEM8 are done in the same way. NOTE: If using a EURO-ZEM8+PSU, the D2+ MUST NOT be connected. ZEM Address 0 (Inputs 35-42), ZEM Address 1 (Inputs 43-50), ZEM Address 2 (Inputs 51-58), ZEM Address 3 (Inputs 59-66). 3.
Enforcer: Installation Manual Wireless ZEM input Addressing: Wireless ZEM Address ZEM32-WE ZEM ZEM ZEM ZEM Inputs Address Address Address Address 0 1 2 3 Wireless ZEM Header Addressing: Wireless ZEM Address ZEM32-WE ZEM ZEM ZEM ZEM Address Address Address Address 0 1 2 3 35-42 43-50 51-58 59-66 0-3 4-7 8-11 OFF OFF OFF OFF ON ON ON ON OFF OFF OFF OFF 3.11 Connecting an Output Expander 1 x Remote Output Expander can be connected to the Enforcer.
Enforcer: Installation Manual 3.12 Digi Wi-Fi (Wi-Fi Module). AMBER LED -On at startup. DIGI-WiFi RED LED Single pulse: No Cloud connection.
Enforcer: Installation Manual Page: 15
Customer Support line (UK Only): +44(0)845 6434 999 (local rate) or +44(0)1709 535225 Hours: 8:00am - 6:30pm, Monday to Friday Email: customer.support@pyronix.com Website: www.pyronix.