Installation Guide

14
IMPORTANT! READ AND FOLLOW ALL INSTALLATION AND MAINTENANCE INSTRUCTIONS, INCLUDING CLEANING
THE UNIT AS SPECIFIED, AND REPLACING GASKETS ANNUALLY, AND PARTS AS NEEDED.
ENGLAND’S STOVE WORKS IS NOT RESPONSIBLE FOR ANY DAMAGE OR INJURY INCURRED DUE TO NEGLECT,
OR DUE TO UNSAFE INSTALLATION OR USAGE OF THIS PRODUCT. CALL TECHNICAL SUPPORT WITH ANY
QUESTIONS.
VENTTERMINATIONCLEARANCES
A)MIN.4FTCLEARANCEBELOWORBESIDEANYDOORORWINDOWTHATOPENS.
B)MIN.1FTCLEARANCEABOVEANYDOORORWINDOWTHATOPENS.
C)MIN.2FTCLEARANCEFROMANYADJACENTBUILDING.
D)MIN.7FTCLEARANCEFROMANYGRADEWHENADJACENTTOPUBLICWALKWAYS.
E)MIN.2FTCLEARANCEABOVEANYGRASS,PLANTS,OROTHERCOMBUSTIBLEMATERIALS.
F)MIN.3FTCLEARANCEFROMAFORCEDAIRINTAKEOFANYAPPLIANCE.
G)MIN.2FTCLEARANCEBELOWEAVESOROVERHANG.
H)MIN.1FTCLEARANCEHORIZONTALLYFROMCOMBUSTIBLEWALL.
I)V
ENTSINSTALLEDWITHMECHANICALEXHAUSTERSSHALLTERMINATENOTLESSTHAN
12
IN
.
(305
MM
)
ABOVETHE
HIGHESTPOINTWHERETHEYPASSTHROUGHTHEROOFSURFACE
.

NotesonterminationofPelletVentPipefrom
NFPA211(2006ed.)Section10.4Termination:10.4.5

(Seealso“INSTALLATION”sectionofmanualANDadditionalnotesabove):
- Not less than three (3) feet above any forced air inlet located within ten (10) feet.
- Not less than four (4) feet below, four (4) feet horizontally from, or one (1) foot above any door,
window or gravity air inlet into any building.
- Not less than two (2) feet from an adjacent building, and not less than seven (7) feet above
grade where located adjacent to public walkways.
The exhaust exit shall be arranged so that the flue gases are not directed so that it will affect people,
overheat combustible structures, or enter buildings. Forced draft systems and all parts of induced
draft systems under positive pressure during operation shall be installed gastight or to prevent
leakage of combustion products into a building. Through-the-wall vents shall not terminate over
public walkways, or where condensate or vapor could create hazards or a nuisance.
Be sure to follow local codes and all manufacturer’s instructions (including exhaust pipe).
Consult a professional installer and/or call Technical Support if you have any questions.