Use and Care Manual
3 
SAFETY NOTICE 
IF THIS UNIT IS NOT PROPERLY INSTALLED, A HOUSE FIRE MAY RESULT. FOR YOUR 
SAFETY AND PROTECTION, FOLLOW ALL OF THE INSTALLATION INSTRUCTIONS. 
INSTALLATION SHOULD BE PERFORMED BY A QUALIFIED INSTALLER. 
CONTACT YOUR LOCAL BUILDING OR FIRE OFFICIALS FOR RESTRICTIONS AND 
INSTALLATION INSPECTIONS REQUIRED IN YOUR AREA. 
IMPORTANT: DO NOT OVER-FIRE. SEE “DO NOT OVER-FIRE YOUR UNIT” IN THE 
“OPERATING INSTRUCTIONS” SECTION. 
CAUTION – Hot Surfaces:  Keep children away. Do not touch during operation. 
SECTION I: FLUE SYSTEM 
Note: Flue systems and flue pipe are not furnished with the unit; they must be 
purchased separately. Follow all manufacturers’ instructions. 
THE UNIT IS NOT TO BE CONNECTED TO A CHIMNEY FLUE SERVING ANOTHER 
APPLIANCE. 
A.  Existing Flue System 
The Add-On furnace is designed to connect to an existing flue system, such as 
masonry or HT Pipe premanufactured flue pipe. If you have a masonry flue system, 
you need to inspect the inner liner very carefully for cracks. If there is no liner in your 
chimney, we recommend you install a stainless steel liner, or have one installed. If 
you have an existing premanufactured flue system, it should be inspected to ensure 
there are no cracks, buckling or warping. We strongly recommend that you have a 
qualified chimney sweep clean and inspect your flue system. 
DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE SERVING ANOTHER 
APPLIANCE. Always try to position the unit as close as possible to the flue servicing 
the unit. The fewer total pipes that are installed, the better the stove will draw. 
B. Flue Size Required 
The proper flue size is determined by the inside diameter of the flue collar on the 
unit. This furnace is equipped with a 6” (6 inch) TOP EXHAUST flue collar. The 
connector pipe should be six inches or larger, but never less in diameter than the 
collar on the stove. The area of the chimney liner must be equal to or greater than 
the area of the collar on the stove. 
Example
: The area of a 6” (6 inch) diameter flue collar is 28.87 square inches; 
therefore, the connector pipe should be at least a 6” (6 inch) diameter pipe and the 
chimney liner must be at least 28.87 square inches but no greater than 84.8 square 
inches. 
Connector pipe should be (at minimum) 24-gauge steel and 18” (18 inches) from a 
combustible wall or ceiling. This unit is tested with single-wall pipe only. 
IMPORTANT: Be sure to refer to the data label and other markings on the 
appliance for additional information, including clearances to combustibles. 










