INSTALLATION AND SET-UP INSTRUCTIONS
SURFACE AND PAD REQUIREMENTS
Your new portable spa must be placed on a uniformly firm,
flat and level surface. A concrete pad 4 inches thick is
best.
In order to prevent flooding of the electrical equipment, the
pad must be such that water will drain away from the spa.
If your spa is located near sprinklers, adjust or cap them so
as not to hit the siding of the spa.
BALCONIES AND DECK REQUIREMENTS
Decking must be constructed to support 85 pounds per
square ft.
Balconies must be constructed to meet current state and
local codes.
Gates must be self-closing and self-latching.
ELECTRICAL REQUIREMENTS (VS-500 & 501)
Your 220-volt spa pack will require a 40-amp dedicated G.F.C.I.
circuit breaker on all models except the “Legacy & Heritage spas”.
Your 110-volt spa pack requires an isolated (no other appliances or
lights on this circuit at any time) 110-volt, 20-amp circuit breaker.
Never tie ground and neutral together.
The minimum conductor ampacity for 110-volt systems is 25-amps;
for 220-volt systems, it is 38-amps on all models except the
“Legacy & Heritage.” The maximum over current protection device
for 110-volt systems is 20-amps; for 220-volt systems, it is 40-amps
on all models except the “Legacy I & II & Heritage I & II”
The minimum conductor ampacity for the 220-volt “Legacy & Heritage”
is
47-amps. The maximum over cur
rent protection device for the
“Legacy I” is 50-amps. The maximum over current protection device
for the “Legacy
II & Heritages” ar
e 60 amps.
Y
our 110-volt or 220-volt spa pack is designed to be
“PERMANENTLY CONNECTED”.