User's Manual

© 2020 EnOcean | www.enocean.com PTM 210 / PTM 215 / PTM 215U / PTM 215J User Manual August 2020 | Page 18/45
USER MANUAL
PTM 210 / PTM 215 / PTM 215U / PTM 215J
DC Step code and later
Executing the special button combination for secure mode 2x nipple SBC or 3x nipple
SBC see chapter 3.3 for details.
Trigger through the NFC interface.
Key Secure Teach-in Parameters are specified as following:
Type of the Teach-in_info in the secure teach-in telegram (Teach_In_Info : Type)
is: 1-PTM.
Info of the Teach-in_info in the secure teach-in telegram (Teach_In_Info : Info)
is: 0-Rocker A / 1-Rocker B.
The opposite nipple (e.g. A0&AI or B0&BI) of the used 2xSBC or 3xSBC define the
rocker value (Rocker A or Rocker B) .
When then Secure Teach-in is triggered by NFC then the rocker is used which was
used to generate energy and transmit the Secure Teach-in telegram. If both or no
rocker was used, then Rocker A is coded.
SLF is set to:
o For implicit RLC (legacy, not recommended)
24 bit MAC, VAES Encryption, 16 bit RLC, RLC no TX:
o For explicit RLC (recommended)
24 bit MAC, VAES Encryption, 24 bit RLC, RLC TX
For more information on the structure of the teach-in telegram please refer to the EnOcean
Security specification [3].
If the teach-in process is not successful, please repeat the procedure. Due to the
enhanced telegram length of teach-in telegrams in secure mode only a single
teach-in sub-telegram is sent at every actuation (no redundancy).
3.3 Switching between modes
PTM 21x can be switched between normal mode and the secure modes by a special button
combination SBC. There are three types of SBC:
2 nipple SBC pressing both nipples of a channel i.e. AI & AO or BI & BO.
This SBC is used to enter the secure mode with implicit RLC legacy, not recom-
mended. The picture below shows both variants of this combination.