DC Step code and later
Executing the special button combination for secure mode 2x nipple SBC or 3x nipple
SBC – see chapter 3.3 for details.
Trigger through the NFC interface.
Key Secure Teach-in Parameters are specified as following:
Type of the Teach-in_info in the secure teach-in telegram (Teach_In_Info : Type)
is: 1-PTM.
Info of the Teach-in_info in the secure teach-in telegram (Teach_In_Info : Info)
is: 0-Rocker A / 1-Rocker B.
The opposite nipple (e.g. A0&AI or B0&BI) of the used 2xSBC or 3xSBC define the
rocker value (Rocker A or Rocker B) .
When then Secure Teach-in is triggered by NFC then the rocker is used which was
used to generate energy and transmit the Secure Teach-in telegram. If both or no
rocker was used, then Rocker A is coded.
SLF is set to:
o For implicit RLC (legacy, not recommended)
24 bit MAC, VAES Encryption, 16 bit RLC, RLC no TX:
o For explicit RLC (recommended)
24 bit MAC, VAES Encryption, 24 bit RLC, RLC TX
For more information on the structure of the teach-in telegram please refer to the EnOcean
Security specification [3].
If the teach-in process is not successful, please repeat the procedure. Due to the
enhanced telegram length of teach-in telegrams in secure mode only a single
teach-in sub-telegram is sent at every actuation (no redundancy).
3.3 Switching between modes
PTM 21x can be switched between normal mode and the secure modes by a special button
combination SBC. There are three types of SBC:
2 nipple SBC – pressing both nipples of a channel i.e. AI & AO or BI & BO.
This SBC is used to enter the secure mode with implicit RLC – legacy, not recom-
mended. The picture below shows both variants of this combination.