5.6.10 ZGP_SEC_CONFIG
The ZGP_SEC_CONFIG register determines the security mode used by PTM 535BZ for the
transmission of ZGP telegrams.
The ZGP_SEC_MODE field defines how the security key is encrypted in the commissioning
telegram. By default, PTM 535BZ uses the ZA09 key to encrypt the security key. Optionally,
PTM 535BZ can use an Install Code (IC) to encrypt the security key. Refer to the Zigbee
Green Power specification [3] for a description of this feature.
The ZGP_KEY_SELECTION field determines which of the two security keys (SECURITY_KEY1
or SECURITY_KEY2) is used to authenticate ZGP data telegrams. SECURITY_KEY1 is used by
default.
The ZGP_BUTTON_COMMISSIONG determines if the LRN button can trigger the transmission
of a commissioning telegram. By default, this is possible. If transmission of commissioning
telegrams is disabled, then the ZGP radio channel has to be selected using ZGP_TX_CHAN-
NEL.
Figure 44 below shows the structure of the ZGP_SEC_CONFIG register.
Figure 44 – ZGP_SEC_CONFIG register structure
The bit fields within the ZGP_SEC_CONFIG register are shown in Table 19 below. The de-
fault settings are shown in bold.
Bit Configuration Option Supported Settings
1:0
ZGP_COMMISSIONING_MODE
Defines the TLK used for transmission
of the ZGP commissioning telegram
0b00: Commissioning telegram uses ZA09 as TLK
0b01: Commissioning telegram uses ZA09 as TLK, IC is supported
0b10: Commissioning telegram uses IC
0b11: RFU
3:1
ZGP_KEY_SELECTION
Selects the security key used for
authentication of ZGP telegrams
0b00: Use SECURITY_KEY1
0b01: Use SECURITY_KEY2
0b10, 0b11: RFU
4
ZGP_BUTTON_COMMISSIONING
Selects if commissioning telegram can
be triggered by the LRN button
0b0: LRN button press with ECO 200 action will trigger
transmission of a commissioning telegram
0b1: LRN button press with ECO 200 action will not trigger
transmission of a commissioning telegram
7:5 RFU 0b000: RFU (Always set to 0b0)
Table 19 – ZGP_TX_CONFIG settings