5.6.17 REQUEST_STATUS
The REQUEST_STATUS field informs the user about the status of the most recent NFC con-
figuration update or NFC functional request. Table 25 shows the encoding of the supported
status reports.
Request (REQUEST_TYPE _SELECTION) Response (REQUEST_STATUS)
Request Type SUCCESS
IN
PROGRESS
PIN
ERROR
PERMISSION
ERROR
PARAMETER
ERROR
USER1
Configuration Update Request 0x31 0x51 0x71 0x91 0xB1
Commissioning Request 0x32 0x52 0x72 0x92 0xB2
Factory Reset Request 0x33 0x53 0x73 0x93 0xB3
ZGP Decommissioning Request 0x34 0x54 0x74 0x94 0xB4
USER2
Configuration Update Request 0x39 0x59 0x79 0x99 0xB9
Commissioning Request 0x3A 0x5A 0x7A 0x9A 0xBA
Factory Reset Request 0x3B 0x5B 0x7B 0x9B 0xBB
ZGP Decommissioning Request 0x3C 0x5C 0x7C 0x9C 0xBC
Table 25 – CONFIGURATION STATUS encoding
The following status can be reported:
SUCCESS
The configuration update or the function request were successfully executed
IN PROGRESS
The configuration update or the functional request is in progress (until the ECO 200
harvester has been actuated sufficiently often so that the requested action can be
completed)
PIN ERROR
The PIN code provided to authenticate the configuration update or the functional re-
quest does not match the expected PIN code
PERMISSION ERROR
The specified request is not allowed (for instance if USER2 tries to change the PIN
code of USER1)
PARAMETER ERROR
The request contains invalid parameters (for instance an undefined configuration reg-
ister value)
5.6.18 DEVICE_STATUS
The DEVICE_STATUS register is an internal register that tracks the PTM 535BZ status during
commissioning actions.