CT Installation Guidelines

!
Getting Started Guide: Four Simple Guidelines for Successful CT Installation All rights reserved. © Enphase 2017
Getting Started: Four Simple Guidelines for Successful Current Transformer Installation
This guide is for the solar energy professional who will install current transformers (CTs) with the Enphase
IQ Envoyor Envoy-S Metered. Refer to the Envoy Installation and Operation Manual for complete installation
instructions and safety warnings.
How CTs Work
The IQ Envoy and the Envoy-S use readings from CTs to report measurement data for
energy production and energy consumption. When current transformers (CTs) are wrapped
around a live wire, the current going through the wire induces a current on the CTs
secondary winding. The current on the secondary winding is proportional to the current on
the original circuit and is used for making measurements.
Polarity Correctness
CTs have a specific polarity, which is determined by the direction of the secondary winding. It is important to
maintain proper CT polarity in all installations, otherwise readings will be negative.
Guidelines
If your meter readings are incorrect, use these guidelines for troubleshooting.
1. CT wire leads must land on the correct
terminals on the Envoy.
IQ Envoy terminal
blocks.
Envoy-S terminal
blocks.
2. The Envoy-S power terminal A and Line 1
consumption and production CTs must be
fed by the same line (phases must match).
To verify using a voltmeter, measure
voltages between endpoints:!
Power terminal A to Line 1 = 0V
Power terminal A to Line 2 = 240V
3. To ensure correct polarity, CT arrows must
be pointing toward the loads.
For production CTs, toward the loads,
away from the Solar PV.
For consumption CTs, toward the
loads, away from the grid.
4. Meters must be enabled using the
Enphase Installer Toolkitmobile app to
report meter data to Enphase Enlighten™.
Select the consumption meter type
based on where you installed the
consumption CTs.
Enable both the production and
consumption meter.