INSTALLATION AND OPERATION MANUAL Enphase IQ8, IQ8+, IQ8M, IQ8A, and IQ8H Microinverters Aug 2022 © 2022 Enphase Energy Inc. All rights reserved.
IQ8 / IQ8+ / IQ8M / IQ8A / IQ8H Micro Installation and Operation Corporate Headquarters Contact Information Enphase Energy Inc. 1420 N. McDowell Blvd. Petaluma, CA 94954 USA enphase.com/en-us/support/contact FCC Compliance This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation.
IQ8 / IQ8+ / IQ8M / IQ8A / IQ8H Micro Installation and Operation Table of Contents 3 Important Safety Information .................................................................................................................................... 5 Read this First ........................................................................................................................................... 5 Product Labels ...................................................................................
IQ8 / IQ8+ / IQ8M / IQ8A / IQ8H Micro Installation and Operation 4 Replacement parts and Cabling................................................................................................................................ 25 Ordering Replacement Parts...................................................................................................................... 25 Enphase IQ Cable Planning and Ordering............................................................................................
IQ8 / IQ8+ / IQ8M / IQ8A / IQ8H Micro Installation and Operation Important Safety Information Read this First This manual contains important instructions for use during installation and maintenance of the IQ 8™ Series Microinverters IMPORTANT: Enphase IQ Series Microinverters require the IQ Cable. An IQ Gateway is required to monitor performance of the IQ Microinverters. The Q Accessories work only with Enphase IQ Series Microinverters.
IQ8 / IQ8+ / IQ8M / IQ8A / IQ8H Micro Installation and Operation WARNINGS: NOTES: Before installing or using the Enphase Microinverter, read all instructions and cautionary markings in the technical description, on the Enphase equipment and on the photovoltaic (PV) equipment. Do not connect Enphase Microinverters to the grid or energize the AC circuit(s) until you have completed all of the installation procedures and have received approval from the electrical utility.
IQ8 / IQ8+ / IQ8M / IQ8A / IQ8H Micro Installation and Operation Enphase IQ Cable Safety DANGER: Risk of electric shock. Do not install the Enphase IQ Cable terminator while power is connected. WARNING: Risk of When stripping the sheath from the IQ Cable, make sure the conductors are not electric shock. Risk damaged. If the exposed wires are damaged, the system may not function properly. of fire Do not leave AC connectors on the IQ Cable uncovered for an extended period.
IQ8 / IQ8+ / IQ8M / IQ8A / IQ8H Micro Installation and Operation Additionally, in a prominent location near the initiator device, a placard or label must be provided with a permanent marking including the following wording: ’PHOTOVOLTAIC SYSTEM EQUIPPED WITH RAPID SHUTDOWN’ The term ‘PHOTOVOLTAIC’ may be replaced with ‘PV.’ The placard, label, or directory shall be reflective, with all letters capitalized and having a minimum height of 9.5 mm (3/8“) in white on red background.
IQ8 / IQ8+ / IQ8M / IQ8A / IQ8H Micro Installation and Operation How the Enphase IQ Series Micros Work The Enphase Microinverter maximizes energy production by using a sophisticated Maximum Power Point Tracking (MPPT) algorithm. Each Enphase Microinverter individually connects to one PV module in your array.
IQ8 / IQ8+ / IQ8M / IQ8A / IQ8H Micro Installation and Operation Planning for Microinverter Installation The Enphase IQ8 Micro is compatible with 60-cell PV modules, and the IQ8+, IQ8M, IQ8A and IQ8H Micro support PV modules with 60-cell or 66 cell or 72 cell in both full and split cell configuration. All of them installs quickly and easily.
IQ8 / IQ8+ / IQ8M / IQ8A / IQ8H Micro Installation and Operation NOTE: *Limits may vary. Refer to local requirements to define the number of microinverters per branch in your area. Utility Service Requirements The Enphase IQ Series Micros work with single-phase service.
IQ8 / IQ8+ / IQ8M / IQ8A / IQ8H Micro Installation and Operation Parts and Tools Required In addition to the microinverters, PV modules, and racking, you will need the following: Enphase Equipment • Enphase IQ Gateway: Required to monitor production. IQ Gateway (model ENV-IQ-AM1-240) communications gateway or IQ Combiner (model X-IQ-AM1-240-B, X-IQ-AM1-240-2, X-IQAM1-240-3, X-IQ-AM1-240-3C).
IQ8 / IQ8+ / IQ8M / IQ8A / IQ8H Micro Installation and Operation Enphase Microinverter Installation Installing the Enphase IQ Series Micros involves several key steps. Each step listed here is detailed in the following pages.
IQ8 / IQ8+ / IQ8M / IQ8A / IQ8H Micro Installation and Operation Step 2: Position the Junction Box A. Verify that AC voltage at the site is within range. Service Type and Voltage: L1-L2 240 VAC Split-Phase 211 to 264 VAC 208 VAC Single-Phase 183 to 229 VAC NOTE: All 208 VAC installations require that you use the Enphase IQ Gateway to commission the Enphase Microinverters to propagate correct grid profile settings for 208 VAC trip points. B.
IQ8 / IQ8+ / IQ8M / IQ8A / IQ8H Micro Installation and Operation Each Enphase Microinverter, IQ Gateway, and IQ Battery have a removable serial number label. Build the installation map by peeling the serial number labels from the microinverter mounting plates and placing the labels on the map. You will also place the Enphase IQ Gateway and IQ Battery serial number on the map after installation.
IQ8 / IQ8+ / IQ8M / IQ8A / IQ8H Micro Installation and Operation WARNING: Risk of electric shock. Risk of fire. Install sealing caps on all unused AC connectors as these connectors become live when the system is energized. Sealing caps are required for protection against moisture ingress. NOTE: If you need to remove a sealing cap, you must use the Enphase Disconnect Tool. See Disconnect a Microinverter” on page 27.
IQ8 / IQ8+ / IQ8M / IQ8A / IQ8H Micro Installation and Operation F. Attach the terminated cable end to the PV racking with a cable clip or tie wrap so that the cable and terminator. Do not touch the roof. WARNING: The terminator cannot be re-used. If you unscrew the nut, you must discard the terminator. Step 8: Complete Installation of the Junction Box A. Connect the Enphase IQ Cable into the junction box. B. Refer to the wiring diagrams on page 47 for more information.
IQ8 / IQ8+ / IQ8M / IQ8A / IQ8H Micro Installation and Operation • Enphase Wireless communication kit enables direct communication between IQ Battery, IQ System Controller, and the Gateway using 2.4 GHz frequency. The kit is connected to one of the USB ports on the IQ Gateway. • An Enphase Mobile Connect™ cellular modem is required unless already present to ensure the best performance of your system. The cellular modem connects to a USB port on the IQ Gateway.
IQ8 / IQ8+ / IQ8M / IQ8A / IQ8H Micro Installation and Operation Enphase Energy System PV Solar Grid Agnostic – Sunlight backup In the PV Solar Grid Agnostic configuration in Enphase Energy System, IQ Smart controller smart switch is installed on the line-side of the main load panels. This allows a properly sized Enphase Energy system to provide power to all loads in the main load panel in the event of a grid outage and PV solar presence.
IQ8 / IQ8+ / IQ8M / IQ8A / IQ8H Micro Installation and Operation In the home essentials backup (main load panel) configuration, IQ System Controller is installed on the line-side of the main load panels rated up to 200A. This allows a properly sized Enphase Energy System to provide power to all loads in the main load panel in the event of a grid outage. In this configuration, the IQ System Controller can be configured with a main breaker to act as the service disconnecting means.
IQ8 / IQ8+ / IQ8M / IQ8A / IQ8H Micro Installation and Operation Troubleshooting Follow all the safety measures described throughout this manual. Qualified personnel can use the following troubleshooting steps if the PV system does not operate correctly. WARNING: Risk of electric shock. Do not attempt to repair the Enphase Microinverter; it contains no user-serviceable parts.
IQ8 / IQ8+ / IQ8M / IQ8A / IQ8H Micro Installation and Operation Method 2: Use Enphase Installer App to Clear the Condition On the list of detected microinverters, a green dot or red square appears to the left of each microinverter serial number. A green dot indicates Status OK. A red square indicates an event for that microinverter. • Tap the to the left of the serial number to view details for a microinverter event.
IQ8 / IQ8+ / IQ8M / IQ8A / IQ8H Micro Installation and Operation E. Using an Enphase disconnect tool, disconnect the AC cable for the microinverter in question from the Enphase IQ Cable. F. Verify that utility power is present at the microinverter by measuring line to line and line to ground at the Enphase IQ Cable connector. G. Visually check that the AC branch circuit connections (Enphase IQ Cable and AC connections) are properly seated. Reseat if necessary.
IQ8 / IQ8+ / IQ8M / IQ8A / IQ8H Micro Installation and Operation Install a Replacement Microinverter A. When the replacement microinverter is available, verify that the AC branch circuit breaker is de-energized. B. Mount the microinverter horizontally bracket side up or vertically • Always place the microinverter under the PV module, protected from direct exposure to rain, sun, and other harmful weather events. Allow a minimum of 1.9cm (3/4”) between the roof and the microinverter. Also allow 1.
IQ8 / IQ8+ / IQ8M / IQ8A / IQ8H Micro Installation and Operation • Press the Device Scan button on the IQ Gateway. The IQ Gateway begins a 15-minute scan to identify all of the microinverters deployed at the site. The Microinverter Communications LED flashes green during the scan. Microinverter Communications LED Device Scan button K. Log in to Enphase Installer platform to use Enphase installer platform’s Array Builder to add the newly detected microinverter to the virtual array. L.
IQ8 / IQ8+ / IQ8M / IQ8A / IQ8H Micro Installation and Operation The Cabling System is flexible enough to adapt to almost any solar design. To determine the cable type, you need, apply the following considerations: • When mixing PV modules in both portrait and landscape orientation, you may need to transition between cable types. See the preceding table for available cable types. • To transition between cable types, install a Field Wireable connector pair.
IQ8 / IQ8+ / IQ8M / IQ8A / IQ8H Micro Installation and Operation Technical Data Technical Considerations Be sure to apply the following when installing the Enphase IQ8 Series Micro System: WARNING: Risk of equipment damage. You must match the DC operating voltage range of the PV module with the allowable input voltage range of the Enphase Microinverter. WARNING: Risk of equipment damage.
IQ8 / IQ8+ / IQ8M / IQ8A / IQ8H Micro Installation and Operation IQ8-60-2-US Microinverter Specifications Topic Enphase IQ8-60-2-US Microinverter Parameters Unit Min DC Parameters Commonly used modules for pairing1 Peak power tracking voltage Operating Voltage Range Maximum Input DC Voltage Minimum/Maximum start voltage Maximum continuous input DC current (module Imp) Maximum DC input short circuit current (module Isc) Overvoltage class DC port DC Port backfeed under single fault Typical Max 235W – 3
IQ8 / IQ8+ / IQ8M / IQ8A / IQ8H Micro Installation and Operation Enphase IQ8-60-2-US Microinverter Parameters Topic Unit Min Typical Max Miscellaneous Parameters Maximum3 microinverters per 20A (max) AC branch circuit 240 VAC (single phase) CEC weighted efficiency 240 VAC (single phase) Total harmonic distortion Ambient temperature range Night-time power consumption 16 % 97% % °C <5 -40 +60 mW Storage temperature range 60 °C -40 +85 Features and Specifications Compatibility 60-cell/120 ha
IQ8 / IQ8+ / IQ8M / IQ8A / IQ8H Micro Installation and Operation IQ8PLUS-72-2-US Microinverter Specifications Enphase IQ8Plus-72-2-US Microinverter Parameters Topic Unit Min Typical Max DC Parameters Commonly used modules for 235W – 440W pairing1 Peak power tracking voltage V 27 45 Operating Voltage Range V 16 58 Maximum Input DC Voltage V Minimum/Maximum start voltage V Maximum continuous input DC current (module Imp) A 12 Maximum DC input short circuit current (module Isc) A 15
IQ8 / IQ8+ / IQ8M / IQ8A / IQ8H Micro Installation and Operation Enphase IQ8PLUS-72-2-US Microinverter Parameters Topic Unit Min Typical Max Miscellaneous Parameters microinverters per 20A (max) AC branch circuit 240 VAC (single phase) Maximum3 13 CEC weighted efficiency 240 VAC (single phase) % 97.
IQ8 / IQ8+ / IQ8M / IQ8A / IQ8H Micro Installation and Operation IQ8M-72-2-US Microinverter Specifications Enphase IQ8M-72-2-US Microinverter Parameters Topic Unit Min Typical Max DC Parameters 260W – 460W Commonly used modules for pairing1 Peak power tracking voltage V 30 45 Operating Voltage Range V 16 58 Maximum Input DC Voltage V Minimum/Maximum start voltage V Maximum continuous input DC current (module Imp) A 12 Maximum DC input short circuit current (module Isc) A 15 60 22 5
IQ8 / IQ8+ / IQ8M / IQ8A / IQ8H Micro Installation and Operation Enphase IQ8M-72-2-US Microinverter Parameters Topic Unit Min Typical Max Miscellaneous Parameters 3 Maximum microinverters per 20A (max) AC branch circuit 240 VAC (single phase) 11 CEC weighted efficiency 240 VAC (single phase) % 97.
IQ8 / IQ8+ / IQ8M / IQ8A / IQ8H Micro Installation and Operation IQ8A-72-2-US Microinverter Specifications Enphase IQ8A-72-2-US Microinverter Parameters Topic Unit Min Typical Max DC Parameters 295W – 500W Commonly used modules for pairing1 Peak power tracking voltage V 32 45 Operating Voltage Range V 16 58 Maximum Input DC Voltage V Minimum/Maximum start voltage V Maximum continuous input DC current (module Imp) A 12 Maximum DC input short circuit current (module Isc) A 15 60 22 5
IQ8 / IQ8+ / IQ8M / IQ8A / IQ8H Micro Installation and Operation Enphase IQ8A-72-2-US Microinverter Parameters Topic Unit Min Typical Max Miscellaneous Parameters 3 Maximum microinverters per 20A (max) AC branch circuit 240 VAC (single phase) 11 CEC weighted efficiency 240 VAC (single phase) % 97.
IQ8 / IQ8+ / IQ8M / IQ8A / IQ8H Micro Installation and Operation IQ8H-240-72-2-US Microinverter Specifications Enphase IQ8H-240-72-2-US Microinverter Parameters Topic Unit Min Typical Max DC Parameters Commonly used modules for 320W – 540W+ pairing1 Peak power tracking voltage V 36 45 Operating Voltage Range V 16 58 Maximum Input DC Voltage V Minimum/Maximum start voltage V Maximum continuous input DC current (module Imp) A 12 Maximum DC input short circuit current (module Isc) A 1
IQ8 / IQ8+ / IQ8M / IQ8A / IQ8H Micro Installation and Operation Enphase IQ8H-240-72-2-US Microinverter Parameters Topic Unit Min Typical Max Miscellaneous Parameters Maximum3 microinverters per 20A (max) AC branch circuit 240 VAC (single phase) 10 CEC weighted efficiency 240 VAC (single phase) % 97.
IQ8 / IQ8+ / IQ8M / IQ8A / IQ8H Micro Installation and Operation IQ8H-208-72-2-US Microinverter Specifications Enphase IQ8H-208-72-2-US Microinverter Parameters Topic Unit Min Typical Max DC Parameters 295W – 500W+ Commonly used modules for pairing1 Peak power tracking voltage V 36 45 Operating Voltage Range V 16 58 Maximum Input DC Voltage V Minimum/Maximum start voltage V Maximum continuous input DC current (module Imp) A 12 Maximum DC input short circuit current (module Isc) A 15
IQ8 / IQ8+ / IQ8M / IQ8A / IQ8H Micro Installation and Operation Enphase IQ8H-208-72-2-US Microinverter Parameters Topic Unit Min Typical Miscellaneous Parameters Maximum3 microinverters per 20A (max) AC branch circuit 208 VAC 9 CEC weighted efficiency 208 VAC % Total harmonic distortion % °C Ambient temperature range Night-time power consumption 97.
IQ8 / IQ8+ / IQ8M / IQ8A / IQ8H Micro Installation and Operation IQ Cable Specifications Specification Value Voltage Rating 600V Voltage withstand test (kV/1min) AC 3.0 Max DC conductor resistance (20ºC) (Ω/km) 5.
IQ8 / IQ8+ / IQ8M / IQ8A / IQ8H Micro Installation and Operation Enphase Installation Map 41 © 2022 Enphase Energy Inc. All rights reserved.
IQ8 / IQ8+ / IQ8M / IQ8A / IQ8H Micro Installation and Operation Sample wiring diagram 42 © 2022 Enphase Energy Inc. All rights reserved.