Method B: Wire in an Enclosure
Though the Envoy-S Standard (ENV-S-AB-120-A) includes an AC power cord, you may hard-wire it instead.
When you hard-wire the Envoy-S, you must install it in a non-metallic, NRTL certified NEMA type 3R-rated
(or better) enclosure with conduit attachment.
DANGER! Risk of electric shock. Be aware that installation of this equipment includes risk of
electric shock. If you wire the Envoy-S at the subpanel, always de-energize the subpanel before
beginning wiring.
a. Use a 15 A maximum circuit breaker for the supply wiring.
b. Make sure supply wiring is 14 AWG rated at 75 degrees C.
c. Locate the screw on the left side of the terminal block door, and loosen it with a screwdriver to unlock
the door.
d. Open the terminal block door and move the shutter to the left. Wire the line and neutral conductors
as shown in the diagram. Tighten terminal block screws to 5 in-lbs.
- Connect Line 1 to A
- Connect Neutral to N