IQ Load Controller Additional Info

Load and Solar Circuit Control using IQ System Controller Auxiliary Contacts
23 © 2021 Enphase Energy Inc. All rights reserved. December 16, 2021
Figure 23: Manual Mode in Enphase App: Shed load when off-grid and restore when generator is
connected
1. Select radio button ‘Manual’
2. Toggle between the 2 options: ‘Not Powered’, ‘Powered’
3. Press ‘Apply’
Installing a custom kit for Load/PV Shedding
As mentioned earlier, The IQ Load Controller(EP-NA-LK02-040) can only be used for controlling
dedicated loads of up to 36A connected on a 45A breaker or for controlling 32A branch circuits or PV
circuits connected on a 40A breaker. The below section of the document provides details on setting up an
installer self-assembled kit for controlling larger loads.
Note: The appendix contains reference BOM’s for 20A, 30A and 40A circuits that can be used as an
alternative to the IQ Load Controller.
Using an external contactor with a 24 Vac coil
24Vac low voltage is created with a control transformer protected with an OCPD such as an inline fuse.
The 24Vac power supply should be connected to a definite purpose contactor via the auxiliary contact.