Load and Solar Circuit Control using IQ System Controller Auxiliary Contacts
27 © 2021 Enphase Energy Inc. All rights reserved. December 16, 2021
Wireless
comms
IQ Combiner
Mobile
connect
`
IQ
combiner
Autotransfor
mer
Generator
Encharge
Enpower 200G
Back up load panel
Wireless
comms
N
Shed PV
Power line
Auxiliary contact wiring 12Vdc
Legend
IQ6/7 Microinverters
AC to DC
Power Supply
Power Relay
w/ 12Vdc Coil
ENVOY
N
To utility grid
120/240V single
phase service only
Contactor w/
120Vac Coil
Note:
NC1 Normally Closed auxiliary contacts used to control a load circuit when
system is in backup mode
The power relay w/ 12Vdc coil is used to control a contactor (w/ 120Vac
coil) which switches the PV branch circuit (s)
The 120Vac coil must be connected to a breaker on the backed up loads
panel via the NO and COM terminals of the power relay
Enpower switches the 12Vdc power to the coil of the power relay to shed or
connect the loads/sub-panel
NO
COM
NC1
Figure 26: PV shedding using external contactor with 120 Vac coil
`
IQ
combiner
Autotransfor
mer
Generator
Encharge
Enpower 200G
Back up load panel
Wireless
comms
N
Note:
NC1 Normally Closed auxiliary contacts used to control a load circuit when
system is in backup mode
The power relay w/ 12Vdc coil is used to control a contactor (w/ 120Vac
coil) which switches the power to the loads or sub-panel
The 120Vac coil must be connected to a breaker on the backed up loads
panel via the NO and COM terminals of the power relay
Enpower switches the 12Vdc power to the coil of the power relay to shed or
connect the loads/sub-panel
Power line
Auxiliary contact wiring 12Vdc
To loads or
sub-panel
AC to DC
Power Supply
Contactor w/
120Vac Coil
Power Relay
w/ 12Vdc Coil
NC1
N
G
NO
COM
Figure 27: Load shedding using external contactor with 120 Vac coil