IQ Load Controller Additional Info

Load and Solar Circuit Control using IQ System Controller Auxiliary Contacts
8 © 2021 Enphase Energy Inc. All rights reserved. December 16, 2021
Basic Mode: Shed load when off-grid
IQ System Controller auxiliary contacts will shed the specific load circuits as soon as the system enters
the off-grid mode. This is done to ensure that a stable microgrid is established. When the grid is back, the
system will reconnect the load.
Mode
MID
Load circuit state
on-grid
Closed
Connected
off-grid
Open
Disconnected
Table 1: Basic mode - Shed load when off-grid
Figure 6: basic mode: Automatically shed load when off-grid using Enphase Installer App
1. Select radio button ‘Basic’
2. Check ‘Home owner can override’ – this will let the home owner to access the settings from
Enphase App Home Owner App
3. Press ‘Save’