IQ system Controller 2 Installation

J ) RSD Aux contact wiring when System Controller 2 is used with
non-IQ8 micros
IQ System Controller 2’s RSD functionality only applies to IQ8 PV mi-
cros connected to the PV lugs/port. The RSD switch will NOT work for
IQ6/7 or M215/25 micros connected to PV lugs/port or the panel
directly.
When using the System Controller 2 with the IQ6/7 or any other micro
inverters apart from the IQ8 Micro inverters, the Rapid Shutdown initia-
tor should not be wired to the aux contacts of the IQ System Controller
2.
In those situations, the Rapid Shutdown aux contacts need to be by-
passed and a seperate rapid shut initiator needs to be wired.
The method for bypassing the Rapid Shutdown aux contacts of System
Controller are as below:
1. Connect the cable header assembly in the auxiliary contacts of NC3
and NC4
2. Use a 12 AWG wire in order to connect the 2 contacts of NC3 and 2
contacts of NC4 as shown in the diagram below.
In order to wire a rapid shut down initiator to System Controller 2
when using a non-IQ8 micro inverter one of the following steps can be
followed
1. The AC circuit breaker installed within the IQ-Combiner.
2. The AC circuit breaker installed within IQ System Controller
3. A dedicated AC disconnect switch located in series with the com
bined PV inverter circuit
When using a non-IQ8 microinverter both the bypass of RSD aux con-
tacts and one of the above RSD wiring needs to be done.
IQ Battery/PV
01 ECO-004882 INITIAL RELEASE
AKC 05OCT20
Wiring Diagram Label,
Enpower 200G-R2
780-00470 02
HENRY W
HENRY W 05OCT20
05OCT20
02 ECO-005166 - MODIFY LABEL MN 12MAR21
NFT/IQ Gateway*
AC Combiner Generator/IQ Gateway*
80
80
IQ Battery/PV AC Combiner Generator
780-00470-02
Remote Rapid
Shutdown
Switch
RSD
Gen I/O
*IQ Gateway can only be put on
one of these two breaker
positions. Refer to the QIG for
instructions.
Grounding Electrode conductor.
Connected to earth when used
as service equipment.
Connected to main service when
not used as service equipment.
IQ Battery
I/O - 1
(24V, 1A)
I/O - 2
(24V, 1A)
Gen - I/O
(24V, 1A)
NO1 NO2 NC1 NC2
NO3
RSD
NC3 NC4
AC Combiner PV/Storage Generator
*The extra lug near the top right side of NFT (auto transformer) is a
manufacturing test terminal intentionally unpopulated with no end user
application.
Cable Header
Assembly
12 AWG wires
Wiring layout to be followed for bypassing the rapid shutdown aux contacts when IQ System Controller 2 is used with non-IQ8 Micros