Installation Guide

IQ 6/IQ 6+ Micro Installation and Operation
© 2017 Enphase Energy Inc. All rights reserved. 141-00034-01
9
Enphase Field Wireable Q Connector Safety Instructions
General Safety
DANGER: Risk of
electric shock.
Improper servicing of the Field Wireable Connector or its components may result in a shock, fire, or
explosion. To reduce these risks, disconnect all wiring before attempting any maintenance.
DANGER: Risk of
electric shock.
Risk of fire.
Before making any connections, verify that the circuit breakers are in the off position. Double check
all wiring before applying power.
Only use electrical system components approved for wet locations, including but not limited to
conduit fittings.
Do not attempt to repair or alter the Enphase Field Wireable Connector.
Make sure the conductors are not damaged. If the exposed wires are damaged, the system may not
function properly.
Do not leave connectors uncovered for an extended period.
WARNING: Risk
of equipment
damage.
This product is intended for operation in an environment having a maximum ambient temperature of
55° C (131° F).
NOTES:
Using unapproved attachments or accessories may result in damage or injury.
To ensure optimal reliability and to meet warranty requirements, install the Enphase Field Wireable
Connectors according to the instructions in this guide.
PV Rapid Shutdown Equipment (PVRSE)
This product is UL Listed as PV Rapid Shut Down Equipment and conforms with NEC-2014 and NEC-2017 section
690.12 and C22.1-2015 Rule 64-218 Rapid Shutdown of PV Systems, for AC and DC conductors, when installed
according to the following requirements:
Microinverters and all DC connections must be installed inside the array boundary. Enphase further
requires that the microinverters and DC connections be installed under the PV module to avoid direct
exposure to rain, UV, and other harmful weather events.
The array boundary is defined as 305 mm (1 ft.) from the array in all directions, or 1 m (3 ft.) form the point
of entry inside a building.
This rapid shutdown system must be provided with an initiating device and (or with) status indicator which must be
installed in a location accessible to first responders, or be connected to an automatic system which initiates rapid
shutdown upon the activation of a system disconnect or activation of another type of emergency system.
The initiator shall be listed and identified as a disconnecting means that plainly indicates whether it is in the “off” or
“on” position. Examples are:
Service disconnecting means
PV system disconnecting means
Readily accessible switch or circuit breaker
The handle position of a switch or circuit breaker is suitable for use as an indicator. Refer to NEC or CSA C22.1-
2015 for more information.
Additionally, in a prominent location near the initiator device, a placard or label must be provided with a permanent
marking including the following wording:
’PHOTOVOLTAIC SYSTEM EQUIPPED WITH RAPID SHUTDOWN’ The term ‘PHOTOVOLTAIC’ may be replaced
with ‘PV.’
The placard, label, or directory shall be reflective, with all letters capitalized and having a minimum height of 9.5 mm
(3/8) in white on red background.