Compatible racking systems for Microinverters

TECHNICAL BRIEF
© 2017 Enphase Energy Inc. All rights reserved. September 2017
1
Compatible Racking Makes and Models for Mounting Enphase
Microinverters
Purpose
This document is not intended to be an exclusive list of racking manufacturers compatible with the Enphase
Microinverter
System. Instead, it lists racking products that Enphase has validated for compatibility through field installations or lab
evaluations. Enphase has validated that the products in this document work with our current product lines, but future
microinverter products may not be compatible.
NOTE: All recommendations included in the Enphase Microinverter Operations and Installation Manual must be
maintained, including, but not limited to:
Do not install the microinverter in a location where it is exposed to prolonged periods of direct
sunlight.
Install the microinverter under the PV module to avoid direct exposure to rain, UV, and other
harmful weather events. Do not expose the AC or DC connectors to rain or condensation
before the connectors are mated.
Install the microinverter at a distance greater than ½” from the module backsheet.
Install the microinverter at a distance greater than ¾” from the roof.
NOTE: All trademarks are the property of their respective owners.
Grounding Options for Enphase Microinverters
Grounding Options for the IQ 6 and IQ 6+ Micros
The Enphase IQ6 and IQ6+ Microinverters include a double-insulated outer enclosure and do not bond the DC
conductors to ground internally. The Q Cable includes only two line (hot) conductors with no neutral and no ground. In an
IQ Microinverter system, the racking, module frames, and IQ Microinverter mounting flange/lid are all bonded with
mounting hardware, such as UL2703 grounding hardware and then grounded as required by the jurisdiction.
Grounding Options for the M-Series and S-Series Microinverters
The Enphase M215-IG, M250, C250, S230, and S280 Microinverters are grounded through the grounding conductor in
the Engage Cable. These microinverters require no additional ground. It is not necessary, but an additional bond can be
provided between the microinverters and the racking systems using UL2703 listed hardware or a listed grounding
washer, such as the WEEB grounding washer from Burndy Electronics. If a grounding path is established between the
microinverters, the racking, and the module frames, it may be acceptable to the jurisdiction to provide the racking and
modules’ equipment grounding through the Enphase Engage Cable. The code case for this grounding application can be
found in an Enphase technical brief at:
http://enphase.com/global/files/Equipment_Grounding_in_an_Enphase_IG_System-v2703.pdf
Grounding Options for the M215 Original and Previous Generation Microinverters
The ground clamp provided on the mounting flange of the M215 Original Enphase Microinverters accepts #8 through #6
AWG grounding electrode conductors. This document also details alternative grounding clip solutions for each rail type, if
available.