System behavior
Power produced in a Sunlight Backup system depends on the solar irradiance at your
location, which can vary depending on cloud cover, shading on the PV panels, time of
the year and other factors. While running o-grid, the system may shutdown if the power
produced is less than what is needed to power the loads. To prevent a system shutdown,
work with your installer and ensure that the system follows the guidance on load selection
provided in the section above.
In the event of a shutdown, the system will automatically recover and restore power to
the essential loads. While recovering, the system will try to identify the load causing the
shutdown and disconnect it to ensure that the other essential loads can be powered on.
This logic is described in detail below:
• When the system shuts down while running o-grid i.e., microgrid collapses, all the
essential loads are powered o.
• If there is sunlight available, the system can take up to two minutes to restart and start
restoring power to the essential loads. At this point the loads that are in Manual mode
and are congured to be powered on will turn on.
• Next the system will power rest of the essential loads in a pre-determined order as
outlined below:
• The order in which the loads are powered on is the same in which the loads are
displayed in the Enphase App (Menu→Settings→Load control).
• Time interval between loads being powered on is 22 seconds.
• If there is a system shutdown within 22 seconds of a load being powered on, the system
considers that load to be responsible for the shutdown.
• If a load causes ve system shutdowns, the system fully disables that load—the load
is powered o and will not be automatically powered on when the system is o-grid.
You can use the Enphase App to turn the load on when irradiance increases (for example
in the afternoon) by changing the load to Manual mode (Menu→Settings→Load control-
>”Load_Name”→Manual).