Install Manual

QUICK INSTALL GUIDE
Installing Enphase IQ 6 and IQ 6+ Microinverters
To install the Enphase IQ 6 and IQ 6+ Microinverters, read and follow all warnings and instructions in this guide and in the Enphase IQ 6 and IQ 6+ Microin-
verter Installation and Operation Manual at: enphase.com/support. Safety warnings are listed on the back of this guide.
The Enphase Microinverter models listed in this guide do not require grounding electrode conductors (GEC), equipment grounding conductors (EGC), or
grounded conductor (neutral). The microinverter has a Class II double-insulated rating, which includes ground fault protection (GFP). To support GFP, use
only PV modules equipped with DC cables labeled PV Wire or PV Cable.
IMPORTANT: Enphase IQ Series Microinverters require the Q Cable and are not compatible with previous Enphase cabling. An IQ Envoy is required to
monitor performance of the IQ Microinverters. The Q Accessories work only with Enphase IQ Series Microinverters.
D ) Check that you have these other items:
AC junction box.
Number 2 and 3 Phillips screwdrivers
Torque wrench, sockets, wrenches for mounting hardware
E ) Protect your system with lightning and/or surge suppression devices. It
is also important to have insurance that protects against lightning and
electrical surges.
F ) Plan your AC branch circuits to meet the following limits for maximum
number of microinverters per branch when protected with a 20-amp
over-current protection device (OCPD).
Maximum
IQ Micros per
AC Branch
Circuit
IQ 6 Micros
(240V single phase)
IQ 6+ Micros
(240V single phase)
16 13
IQ 6 Micros
(208V single phase)
IQ 6+ Micros
(208V single phase)
14 11
G ) Size the AC wire gauge to account for voltage rise. Select the correct
wire size based on the distance from the beginning of the Enphase Q
Cable to the breaker in the load center. Design for a voltage rise total of
less than 2% for the sections from the Enphase Q Cable to the breaker
in the load center. Refer to the Voltage Rise Technical Brief at
enphase.com/support for more information.
Best practice: Center-feed the branch circuit to minimize voltage rise in
a fully-populated branch.
PREPARATION
A ) Download the Enphase Installer Toolkit mobile app and
open it to log in to your Enlighten account. With this app,
you can scan microinverter serial numbers and connect
to the Enphase IQ Envoy to track system installation
progress. To download, go to enphase.com/toolkit or
scan the QR code at right.
B ) Refer to the following table and check PV module electrical compati-
bility at: enphase.com/en-us/support/module-compatibility.
Microinverter model DC Connector type PV module cell count
IQ6-60-2-US MC-4 locking type Pair only with 60-cell
modules.
IQ6PLUS-72-2-US MC-4 locking type Pair with 60- or 72-cell
modules.
C ) In addition to the Enphase Microinverters, PV modules and racking,
you will need these Enphase items:
An Enphase IQ Envoy (model ENV-IQ-AM1-240) communications
gate-way or IQ Combiner (model X-IQ-AM1-240-B or X-IQ-AM1-240-2)
is required to monitor solar production.
Tie wraps or cable clips (Q-CLIP-100)
Enphase Sealing Caps (Q-SEAL-10): for any unused connectors on
the Enphase Q Cable
Enphase Terminator (Q-TERM-10): one needed at the end of each AC
cable segment
Enphase Disconnect Tool (Q-DISC-10)
Enphase Q Cable:
Cable model Connector
spacing
PV module
orientation
Connector count
per box
Q-12-10-240 1.3m Portrait 240
Q-12-17-240 2.0m Landscape (60-cell) 240
Q-12-20-200 2.3m Landscape (72-cell) 200
Allows for 30 cm of cable slack.
AC connector
Enphase
IQ 6 Micro or IQ 6+ Micro
DC connector
AC junction box
terminator
Enphase
Q Cable
Tie wraps or
cable clips
Enphase
disconnect
tool

Summary of content (5 pages)