Planning for an IQ Microinverter System
© 2018 Enphase Energy Inc. All rights reserved. December 13, 2018
7
Sealing Caps
You must seal each unused Q Cable connector with a watertight sealing cap (Q-SEAL).
Seal each unused connector on the Q Aggregator with a male sealing cap. Also, during construction, you
must use male sealing caps to temporarily seal any exposed IQ Micro connectors, that are not connected to
the Q Cable, to protect against moisture or water damage at the exposed connector.
Q Terminator
Install a terminator (Q-TERM) on any cut end of Q Cable that is not terminated with a Field Wireable Q
Connector.
Male connector on Q Cable
Female Sealing Cap (Q-SEAL)
Male Sealing Cap
(Q-BA-CAP)
Q Terminator on each cut end of
Q Cable