- IQ Micros on a Three Phase System
- IQ Commercial Envoy
- Q Cable and IQ Microinverter Accessories
- Commercial IQ System Design
- Three-phase, 208Y/120V System Design
- 208Y/120V Electrical Service Conceptual Schematic
- Ampacity Calculations for 208V Branch Circuits on Two-Pole Circuit Breakers
- Ampacity Calculations for Three-Phase Feeders to 208Y/120V Solar Subpanel
- Example 208Y/120V Electrical Schematic
- Example 208Y/120V Basic Building Block Single Line Diagram for IQ 7+ with optional field-assembled Micro panel, keeping within maximum 249 Micros per Envoy recommendation.
- Interconnecting IQ Microinverters to Other Voltages
- Three-phase, 208Y/120V System Design
- Multiple IQ Commercial Envoys on a Single Site — Filtering Communication Domains
- Splicing Q Cable and Raw Q Cable with Junction Boxes
- Wire Management of AC and DC Cables Under Array
- AC Wire Management at the Junction Box
- Installing IQ Microinverters with Frame Mount Bracket
- Appendix A: Lightning and Surge Suppression in Commercial Systems
- Appendix B: Phase Loss Protection
Planning a Commercial IQ Microinverter System – North America
© 2020 Enphase Energy Inc. All rights reserved. January 27, 2020
3
IQ Commercial Envoy
When designing a three-phase, commercial-scale system, it is critical to install an IQ Commercial Envoy
(model ENV-IQ-AM3-3P). It can be used with three-phase systems for monitoring and maintenance of all
microinverters which are connected in the same Envoy communication domain. Three production CTs, which
come included with the IQ Commercial Envoy, are used when installed on a three-phase system for system
production metering.
Design recommendations for good PLC communications between the Envoy and micros:
1. Do not exceed 249 IQ micros per Envoy. Consult Enphase if this limit needs to be exceeded.
2. Install the Envoy as close as possible to the microinverters. Consult Enphase if you need to exceed
75 meters (246 feet) conductor length between the Envoy and the last micro in the circuit.
3. Install a line communication filter or use a delta-wye isolation transformer(s) to isolate Envoy
domains. Filtering is mandatory when multiple Envoys are installed to separate communication
domains.
4. Do not mix Envoy domain circuits when distributing power. Keep parallel circuit runs of
different communication domains physically separated by at least 12 inches.
The IQ Commercial Envoy is to be used solely for 208Y/120V three phase applications and provides
integrated PV production metering (+/- 0.5%) with included three 200A continuous rated production CTs, and
optional consumption monitoring (+/- 2.5%). The IQ Commercial Envoy is required for applications using
Power Export Limiting (PEL), however PEL only works in systems with a single IQ Commercial Envoy and
where the optional consumption CTs can fit around the total service load conductors. The maximum
consumption CT capacity of a single Envoy is 400A (paralleling two 200A CTs per phase).
Do not install the IQ Combiner, IQ Combiner+, IQ Combiner 3, or IQ Combiner 3C in three phase
applications; it is only for single-phase applications.
IQ Commercial Envoy
Select the Envoy model for your system depending on metering requirement and on voltage configuration at
the solar subpanel:
Voltage Configuration
(at Solar Subpanel)
Envoy Type
Envoy SKU
3-Phase Metering
208Y/120
IQ Commercial Envoy
ENV-IQ-AM3-3P
Available