User manual

2. Configuration
2.1 Main Device Parameters
In order for the device to function properly, both the RS-485 serial communication parameters
and the network parameters have to be configured correctly. Incorrect or incomplete
configuration of these parameters can degrade the system performance and even disrupt the
existing network infrastructure.
Network Settings Serial Port Settings
Connection
Setting
Server Baud Rate 9600
DHCP Off Data Bit 8
WEB Access Off Stop Bit 1
Log-in Timeout 120000 ms Parity None
Link Auto Timeout 2000 ms
IP Address 192.168.2 240 Delay 50 ms
Gateway Address 192.168.2.1
Subnet Mask 255.255.255.0
Port 502
Operating Mode
MODBUS/TC
P
Table 2. EMG Factory Default Values