Instructions
6
Connection Diagram
1- Voltage Inputs 3- Auxiliary Supply Input
5- RS-4854- Current Inputs
2- Relay Outputs
Terminal Structure;
Connection Range Klemens Tipi
1 Voltage Inputs 3 x 10 – 480 VAC 50/60Hz 4 x 7.62 mm socket
2.5 mm², 4 mm²
2 Relay Outputs 2 x 250 VAC 5A 1250 VA 4 x 5.08 mm socket
2.5 mm² / 4 mm²
3 Auxiliary supply input 100-270 VAC / 50-60 Hz 3 x 5.08 mm socket
2.5 mm² / 4 mm²
4 Current Inputs 3 x 0.05 – 5.5A / AC 50-60 Hz 6 x 5.08 mm socket
2.5 mm² / 4 mm²
5 RS-485 Max. ±12V 3 x 3.81 mm socket
1.5 mm² / 2.5 mm