EPC-12 User Manual www.entes.com.
Warnings PULSE CONCENTRATOR User Manual EPC-12 WARNING Ignoring the instructions in this manual may result in serious injuries or death. Disconnect all power supply inputs before connecting the device. Do not remove the front panel when device is connected to the mains. Do not clean the device with solvents alike. Only clean with dry cloth. Verify correct terminal connections before energizing the device. Contact your authorized reseller in case problems occur with your device.
Index 1. INTRODUCTION............................................................................................ 4 1.1. APPLICATIONS................................................................... 4 1.2. GENERAL FEATURES............................................................ 4 1.3. FRONT PANEL............................................................................ 5 1.4. HARDWARE FEATURES...................................................... 6 2. UTILIZATION OF DEVICE...........................
6) Activating password protection and defining a new password, 7) Changing the log save period, 8) Activating DST(Daylight Savings Time), 9) Holiday, saturday, sunday and week day tariffs can be programmed (8 for each)*, 10) Monitoring counters with tariff and total counters, 11) Resetting counters with tariff and total counters, 12) Assigning index to counters with tariff when Counter Set from device menu is activated, 13) Monitoring date and time, tariff, next record number to be written and alarm states
2. UTILIZATION OF DEVICE For security reasons, only a portion of the settings are permitted to be changed directly from the device. Therefore, device settings will be explained under two headlines as Changed from the Device and Changed via Modbus protocol using PC.
Main Menus There are 3 main menus on the device. These menus are RS-485, PASSWORD and ESCAPE. When SET button is pressed for 3 seconds on the monitoring screen, main menu is accessed. Sub-menus are accessed while on any main menu by pressing set button. If the password protection feature is active, a password* will be asked before entering the main menu when set button is pressed for 3 seconds. * Factory setting for password is 1234. Enter your password with Up, Down and Set buttons.
Selecting Parity value You can select Parity option as No, Odd or Even. Selecting Baud Rate value You can select Baud Rate value as 1200, 2400, 4800, 9600, 19200 or 38400 bps. Parity No Baud Rate 9600 Baud Rate 19200 Baud Rate 38400 Baud Rate 9600 Baud Rate 1200 Baud Rate 4800 Baud Rate 2400 Baud Rate 19200 Parity Odd Parity Even Parity Even Entering Address information Address information can be entered between 1 and 247.
Counter Set Setting (Activating index writing to counters with tariff) If Counter Set menu is set as Disable, no other value than 0 is allowed to be written to counters with tariffs with the configuration software. However; if Counter Set menu is set as Enable, you can write index between 0 and 4.294.967.295 (2 word) to counters with tariff.
Change (Changing user password) User password is changed in this menu.
ESCAPE Save No Save Yes Monitoring Screen Saved! Commited change is not saved! Commited change is saved! 17 2.2. Settings that are changed from the PC 2.2.1. RS-485 Settings You can change RS-485 settings that you can change from the device such as Baud Rate, Parity and Address by using the configuration software. When you change EPC-12 RS-485 settings, communication between device and PC will be disconnected.
ADDRESS ADDRESS (HEX) 32771 8003 32772 32773 32774 8004 8005 8006 PASSWORD ACTIVATION: 0 = Inactive 1 = Active REGISTER R/W RANGE FORMAT PASSWORD R/W 0-9999 unsigned int PASSWORD ACTIVATION R/W R/W R/W 0-1 1-60 0-1 unsigned int unsigned int unsigned int LOG RECORD PERIOD DAYLIGHT SAVINGS TIME DAYLIGHT SAVINGS TIME: 0 = Inactive 1 = Active 2.2.3.
R/W RANGE FORMAT IN6 DENOMINATOR R/W 1-65535 unsigned int 32793 32794 32795 8019 801A 801B IN7 DENOMINATOR IN8 DENOMINATOR IN9 DENOMINATOR R/W R/W R/W 1-65535 1-65535 1-65535 unsigned int unsigned int unsigned int 32796 801C IN10 DENOMINATOR R/W 1-65535 unsigned int 32797 32798 32799 32800 801D 801E 801F 8020 IN11 DENOMINATOR IN12 DENOMINATOR IN1 UNIT IN2 UNIT R/W R/W R/W R/W 1-65535 1-65535 0-54 0-54 unsigned int unsigned int unsigned int unsigned int 32801 32802 32803 32804 32805
DAY OF THE WEEK: 0 = Sunday 1 = Monday 2 = Tuesday 3 = Wednesday 4 = Thursday 5 = Friday 6 = Saturday Holiday Tariff Settings Starting year, starting month, starting day, starting hour and ending year, ending month, ending day, ending hour values and finally, the number of the tariff that will be active in that time interval are entered in that order under holiday tariff settings.
R/W RANGE FORMAT STARTING YEAR / MONTH R/W 0-99 I 1-12 unsigned int 32849 32850 32851 8051 8052 8053 STARTING DAY /HOUR ENDING YEAR / MONTH ENDING DAY / HOUR R/W R/W R/W 1-31 I 0-23 0-99 I 1-12 1-31 I 0-24 unsigned int unsigned int unsigned int 32852 8054 R/W 0-8 unsigned int 32853 32854 32855 32856 8055 8056 8057 8058 TARIFF STARTING YEAR / MONTH R/W R/W R/W R/W 0-99 I 1-12 unsigned int unsigned int unsigned int unsigned int 32857 32858 32859 32860 32861 8059 805A 805B 805C 805D T
STARTING HOUR / MINUTE: Hour (between 0 - 23), Minute (between 0 - 59) can be entered. Value to be written = Hour x 256 + Minute ENDING HOUR / MINUTE: Hour (between 0 - 24), Minute (between 0 - 59) can be entered. Value to be written = Hour x 256 + Minute ADDRESS 32888 32889 32890 SATURDAY TARIFF SETTINGS Saturday Sunday Week Day Tariff Settings Additional to the holiday tariff setting, the device also has tariff settings that repeat each week.
32911 SUNDAY TARIFF SETTINGS ADDRESS 32912 32913 32914 32915 32916 32917 32918 32919 32920 32921 32922 32923 32924 REGISTER R/W RANGE FORMAT 0-8 0-23 I 0-59 unsigned int TARIFF R/W 808D 808E STARTING HOUR / MINUTE 808F TARIFF R/W R/W R/W ADDRESS (HEX) 8090 ENDING HOUR / MINUTE 0-24 I 0-59 0-8 unsigned int unsigned int unsigned int REGISTER R/W RANGE FORMAT STARTING HOUR / MINUTE R/W 0-23 I 0-59 unsigned int ENDING HOUR / MINUTE 0-24 I 0-59 0-8 0-23 I 0-59 unsigned int unsigned
WEEKDAY TARIFF SETTINGS 32942 32943 32944 32945 32946 32947 32948 32949 32950 32951 32952 32953 32954 32955 32956 32957 32958 32959 ADDRESS (HEX) 80AE 80AF 80B0 REGISTER R/W RANGE FORMAT STARTING HOUR / MINUTE R/W 0-23 I 0-59 unsigned int ENDING HOUR / MINUTE 0-24 I 0-59 0-8 0-23 I 0-59 unsigned int unsigned int unsigned int 80B1 80B2 STARTING HOUR / MINUTE R/W R/W R/W ENDING HOUR / MINUTE R/W 0-24 I 0-59 unsigned int 80B3 80B4 80B5 TARIFF R/W R/W R/W R/W 0-8 0-23 I 0-59 unsigned in
0 1 2 3 4 ADDRESS (HEX) 0 1 2 3 REGISTER IN1 TOTAL COUNTER R/W R/W RANGE 0 FORMAT ADDRESS unsigned long long int 16 17 18 19 20 4 5 6 7 8 9 10 11 12 13 5 6 7 8 9 A B C D 14 15 E F IN2 TOTAL COUNTER R/W 0 unsigned long long int IN3 TOTAL COUNTER R/W 0 unsigned long long int IN4 TOTAL COUNTER R/W 0 unsigned long long int 33 TOTAL COUNTER INDEXES TOTAL COUNTER INDEXES ADDRESS 21 22 23 24 25 26 27 28 29 30 31 ADDRESS (HEX) 10 11 12 13 REGISTER R/W RANGE FORMAT IN5 TOTAL CO
2.2.8. Counter Indexes with Tariff In order to change index values, Counter Set menü on the EPC-12 device has to set as Enable.
64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 ADDRESS REGISTER R/W (HEX) 40 IN9 T1 COUNTER WITH TARIFF R/W 41 42 IN10 T1 COUNTER WITH TARIFF R/W 43 44 45 46 47 48 49 4A 4B 4C 4D 4E 4F 50 51 IN11 T1 COUNTER WITH TARIFF R/W IN12 T1 COUNTER WITH TARIFF R/W IN1 T2 COUNTER WITH TARIFF R/W IN2 T2 COUNTER WITH TARIFF R/W IN3 T2 COUNTER WITH TARIFF R/W IN4 T2 COUNTER WITH TARIFF R/W IN5 T2 COUNTER WITH TARIFF R/W 37 RANGE FORMAT 0-65535 0-65535 0-65535 0-65535 0-65535 0-65535 0-65535 0-65535
100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 ADDRESS REGISTER (HEX) 64 IN3 T3 COUNTER WITH TARIFF 65 66 IN4 T3 COUNTER WITH TARIFF 67 68 69 6A 6B 6C 6D 6E 6F 70 71 72 73 74 75 IN5 T3 COUNTER WITH TARIFF R/W R/W R/W R/W IN6 T3 COUNTER WITH TARIFF R/W IN7 T3 COUNTER WITH TARIFF R/W IN8 T3 COUNTER WITH TARIFF R/W IN9 T3 COUNTER WITH TARIFF R/W IN10 T3 COUNTER WITH TARIFF R/W IN11 T3 COUNTER WITH TARIFF R/W 39 RANGE FORMAT 0-65535 0-65535 0-65535 0-65535 0-65535 0-6
136 137 138 139 140 141 142 143 144 145 146 147 148 149 150 151 152 153 ADDRESS REGISTER (HEX) 88 IN9 T4 COUNTER WITH TARIFF 89 8A IN10 T4 COUNTER WITH TARIFF 8B 8C 8D 8E 8F 90 91 92 93 94 95 96 97 98 99 IN11 T4 COUNTER WITH TARIFF R/W R/W R/W R/W IN12 T4 COUNTER WITH TARIFF R/W IN1 T5 COUNTER WITH TARIFF R/W IN2 T5 COUNTER WITH TARIFF R/W IN3 T5 COUNTER WITH TARIFF R/W IN4 T5 COUNTER WITH TARIFF R/W IN5 T5 COUNTER WITH TARIFF R/W 41 RANGE FORMAT 0-65535 0-65535 0-65535 0-65535 0-65535 0
172 173 174 175 176 177 178 179 180 181 182 183 184 185 186 187 188 189 ADDRESS REGISTER (HEX) AC IN3 T6 COUNTER WITH TARIFF AD AE IN4 T6 COUNTER WITH TARIFF AF B0 B1 B2 B3 B4 B5 B6 B7 B8 B9 BA BB BC BD IN5 T6 COUNTER WITH TARIFF R/W R/W R/W R/W IN6 T6 COUNTER WITH TARIFF R/W IN7 T6 COUNTER WITH TARIFF R/W IN8 T6 COUNTER WITH TARIFF R/W IN9 T6 COUNTER WITH TARIFF R/W IN10 T6 COUNTER WITH TARIFF R/W IN11 T6 COUNTER WITH TARIFF R/W 43 RANGE FORMAT 0-65535 0-65535 0-65535 0-65535 0-65535 0-6
208 209 210 211 212 213 214 215 216 217 218 219 220 221 222 223 224 225 ADDRESS REGISTER R/W (HEX) D0 IN9 T7 COUNTER WITH TARIFF R/W D1 D2 IN10 T7 COUNTER WITH TARIFF R/W D3 D4 D5 D6 D7 D8 D9 DA DB DC DD DE DF E0 E1 IN11 T7 COUNTER WITH TARIFF R/W IN12 T7 COUNTER WITH TARIFF R/W IN1 T8 COUNTER WITH TARIFF R/W IN2 T8 COUNTER WITH TARIFF R/W IN3 T8 COUNTER WITH TARIFF R/W IN4 T8 COUNTER WITH TARIFF R/W IN5 T8 COUNTER WITH TARIFF R/W 45 RANGE FORMAT 0-65535 0-65535 0-65535 0-65535 0-65535 0-655
ADDRESS DEVICE STATUS 240 241 242 243 ADDRESS (HEX) F0 F1 F2 F3 REGISTER R/W RANGE FORMAT DAY R 1-31 unsigned int MONTH YEAR HOUR R R R 1-12 0-99 0-23 unsigned int unsigned int unsigned int 244 F4 MINUTE R 0-59 unsigned int 245 246 247 248 F5 F6 F7 F8 SECOND DAY OF THE WEEK TARIFF RECORD NO TO BE WRITTEN NEXT R R R R 0-59 0-6 1-8 0-16383 unsigned int unsigned int unsigned int unsigned int 249 F9 ALARM R 0-7 unsigned int 2.3.
4.1.CONNECTION DIAGRAM 4.DIMENSIONS 71,2 61,6 44,9 90 48 58 26,5 31,5 38,9 90 * Common Lead (Using any one of them will suffice.) When a counter with NPN output is connected to EPC-12, collector lead is connected to In (+) input and emitter lead is connected to Com (-) input. When a counter with PNP output is connected to EPC-12, emitter lead is connected to In (+) input and collector lead is connected to Com (-) input. Dimensions are in millimeters.
BY USING A REPEATER, 247 DEVICES CAN BE CONNECTED TO THE SAME LINE. RS485/RS232 A MAX. OF 31 DEVICES CAN BE CONNECTED TO THE SAME LINE MAX. 1200 mt. B A TR B A GND EPC-12 -31. ... or RS-485/USB CONVERTER MAX. 1200 M MAX. 1200 M RS-485 / 232 or RS-485 / USB CONVERTER B A GND PC GND TRB A GND TR B A GND EPC-12 -2. TR B A GND EPC-12 -1. EPC-12 247 51 ... ...
............
5. TECHNICAL DATA Operating Voltage (Un) Operating Frequency (f) Supply Input Power Consumption Communication (Insulated) Baud Rate Adress Parity Stop Bit Max Communication Distance Pulse Inputs (12 pcs, Insulated) Minimum Pulse Duration Minimum Time Between Pulses Minimum pulse period Maximum Pulse Frequency Maximum Contact Resistance Pulse Voltage Trigger Edge Distance between meters to be connected to EPC-12 Total Counter Capacity = Please see device labels.