User manual

5. TECHNICAL DATA
Operating Voltage (Un) = Please see device labels.
Operating Frequency (f) = 45-65Hz
Supply Input Power Consumption = <5VA
Communication (Insulated) = MODBUS RTU (RS485)
Baud Rate = 1200  38400 bps
Adress = 1  247
Parity = No, Odd, Even
Stop Bit = 1
Max Communication Distance = 1200 m (MODBUS/RS-485 side, using signal amplifier)
Pulse Inputs (12 pcs, Insulated) = Complies with EN 62053-31.
Minimum Pulse Duration = 10 ms
Minimum Time Between Pulses = 30 ms
Minimum pulse period = 60 ms
Maximum Pulse Frequency = 16 Hz
Maximum Contact Resistance = 800 Ohm
Pulse Voltage = 10-12V
Trigger Edge = Rising and Pulse width control
Distance between meters
to be connected to EPC-12 = 1000 m
Total Counter Capacity = 34.359.738.360
Cable Thickness for RS-485 Connection = CAT 5 cable
Weight = 456,4 gr
Internal Memory = 2MB
55
Ambient Temperature = -25...+55 C
Storage Temperature = -25...+70 C
Humidity = %95
Display = Backlight 2x12 LCD
Dimensions = DIN4 (PK27)
Device Protection Class = Double Insulated
Front panel = IP40
Terminals = IP20
Enclosure Material = Nonflammable
Installation = Rail mount
Cable Thickness for Voltage Connection = max. 2.5 mm
Cable Thickness for Pulse Connection = max. 2.5 mm
Factory Default Settings
Baud Rate = 9600
Parity = No
Address = 1
Counter Set = Disable
PASSWORD = 1234
PASSWORD Enable = No
Log Save Period = 30 min.
Daylight Savings Time application = Active
Multiplier = 1
Denominator = 1
Unit = None
Tariff = None
Counters = 0
Alarm = Normal