MPR-2 SERIES NETWORK ANALYZER OPERATING MANUAL Index SAFETY AND WARNING ................................................................................................................................3 Attention ..................................................................................................................................................3 Safety ...............................................................................................................................................
Current, Voltage and Frequency Screens ..........................................................................................19 Power and Power Factor Screens ......................................................................................................21 Energy and Harmonic Screens ..........................................................................................................23 Minimum, Maximum and Demand Screens .......................................................................
SAFETY AND WARNING Attention If the following instructions are not carefully followed, the circumstances which can cause death and serious injuries might happen. The installation of the device must be performed by the qualified and trained personnel. Please, cut the whole power while installing the device. Please, use a suitable circuit breaker on the installation terminal. You must connect the power lead-ins of the device by using a current transformer.
Safety Please, read the entire operating manual before using the device. Connect a button or a circuit breaker between the mains and the supply inputs of the device. The button or circuit breaker to be connected should be close to the device. It should be labeled that the button or circuit breaker to be connected will be used for separating the device from the mains. This device is used for analyzing the electricity mains and it must not be used for main protection function.
OPERATING CONDITIONS Operating Conditions Value Range Operating voltage 95 - 270 VAC/VDC ,12 – 50 VDC (for D series) (Tolerances up to ± 10%) Frequency Range 50 ~ 60 Hz.
INTRODUCTION General Specifications Wide supply voltage range (95 – 270 VAC-DC,12 – 50 VDC (for D series)) Illuminated special FSTN display 3 voltage measurement input 3 current measurement input 4 different language options.
Changeable transformer settings Measurement by 5 different connections: 3-phsae 4-wire, 3-phase 3-wire, 3-phase Aron, 3phase 4-wire balanced, 3-phase 3-wire balanced Adjustable LCD display contrast Adjustable LCD Backlight on/off time Adjustable Demand and Integration time Summer-Winter time application Applications This is a MPR-2 series 3-phase mains analyzer.
Appearance and Interface The appearance of the Device Interface is as below: 24 25 26 27 LCD Symbols 1. Displays the region where the main runs. 2. Indicates that the displayed value is negative. 3. Displays that the measurement is inductive or capacitive.
4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. 17. 18. 19. 20. 21. 22. 23. Displays that the digital output is active. Displays that the pulse input is active. Flashes if password is needed while entering the programming menu. Flashes if RTC is reset and stays on until the RTC is set. Indicates that there is a phase sequence fault. Indicates that there is a warning. Flashes when the alarm output is active. Indicates that the communication is active. Indicates that the measurement is Power Factor or Cos φ.
Terminal Structures The terminal structures according to the models are described in this section: Structure of the MPR-27S-23 Terminal: Current Terminals: K1, L1, K2, L2, K3, L3 An external current transformer must be used for the 3-phase system connection to these terminals where the current up to 5A can be input. Supply Terminals: A1, A2 Please, apply 85-300 VAC/DC supply connection through these terminals.
As the OC terminal will be the joint point (reference), the O1 and O2 terminals are used as insulated outputs. As it can be seen from the following figure, these Open Collector outputs should be fed by an external supply for operation. 5-30 VDC Relay Coil O1 O2 MPR 2X OC Analog Output Terminals: AOC, AVO, AIO As the AOC terminal will be the joint point (reference), the analogue current or voltage output is ensured respectively through the AIO and AVO terminals.
Structure of the MPR-26S-21 Terminal: Different from the MPR27S-23, these terminals which are used for relay output are the terminals next to the voltage terminals. They are indicated with the key symbol on the front view. The terminal structure of the MPR26S-21 model is as in the following: Structure of the MPR-25S-22 Terminal: Different from the MPR27S-23, there is not any analogue output terminals on the MPR25S-22 model.
Structure of the MPR-24S Terminal: Different from the other terminal models, MPR24S model dost not have any I/O terminal. This terminal has only supply and measurement terminals.
CONNECTION TYPES As there are shunts at the current measurement inputs of the device, it is mandatory to use a current transformer except for the connections of current inputs. If, the device will be used on the same current line by means of analyzers with other shunts, it is recommended that the device is located at the extreme point. The device has 5 different connection types.
3P3W (Three-Phase Three-Wire) Connection As it is seen below, three voltage and three current connections are established in this connection type. ARON Connection Three voltage and two current connections are established in this connection type. As it is seen in the following figure, the current connections are established with the 1st and 3rd phases.
3P4W BLN (Three-Phase Four-Wire Balanced) Connection Four voltages and one current connection are established in this connection type. The device displays the value measured at the current input connected to the first phase on its screen for other phases in the same value. 3P3W BLN (Three-Phase Three-Wire Balanced) Connection Three voltage and one current connections are established in this connection type.
Connection Control After, the connections of the device are completed, you can check the connection you established by using the test functionality. The device switches into the connection test mode if the BACK button is pushed for 3 seconds. In this mode, at least 20% of the normal voltage and 10% of the nominal current must be applied on the measurement inputs of the device and the angle difference between the voltage and current inputs should be lower than 30 degrees.
Communication Line Termination Resistance If, the communication distance of RS485 lines is longer than 10 meters and there are more than one devices on the line, a 120 Ω line termination resistance should be installed between the A and B ends of the farthest device of the communication terminal. For this process, as it is seen from the following figure, it is enough to short-circuit the GND and TR terminals of the device.
OPERATING DEVICE Instant Measurement Screens In this section, the screens which will be displayed by the buttons of the device while the device is in the measurement mode are described.
NAME OF THE BUTTON DISPLAYED MEASUREMENT SCREEN BACK (VIF) VOLTAGE UNBALANCE NAME OF THE BUTTON DISPLAYED MEASUREMENT SCREEN BACK (VIF) CURRENT UNBALANCE NAME OF THE BUTTON DISPLAYED MEASUREMENT SCREEN BACK (VIF) HOUR COUNTER 1 NAME OF THE BUTTON DISPLAYED MEASUREMENT SCREEN BACK (VIF) HOUR COUNTER 2 20
Power and Power Factor Screens NAME OF THE BUTTON DISPLAYED MEASUREMENT SCREEN DOWN (P PF) TOTAL POWERS NAME OF THE BUTTON DISPLAYED MEASUREMENT SCREEN DOWN (P PF) ACTIVE POWER NAME OF THE BUTTON DISPLAYED MEASUREMENT SCREEN DOWN (P PF) REACTIVE POWER 21
NAME OF THE BUTTON DISPLAYED MEASUREMENT SCREEN DOWN (P PF) APPARENT POWER NAME OF THE BUTTON DISPLAYED MEASUREMENT SCREEN DOWN (P PF) POWER FACTOR NAME OF THE BUTTON DISPLAYED MEASUREMENT SCREEN DOWN (P PF) COS φ 22
Energy and Harmonic Screens NAME OF THE BUTTON DISPLAYED MEASUREMENT SCREEN UP (E H) THD L-N NAME OF THE BUTTON DISPLAYED MEASUREMENT SCREEN UP (E H) THD L-L NAME OF THE BUTTON DISPLAYED MEASUREMENT SCREEN UP (E H) THD IN 23
NAME OF THE BUTTON DISPLAYED MEASUREMENT SCREEN UP (E H) IMPORT ACTIVE ENERGY NAME OF THE BUTTON DISPLAYED MEASUREMENT SCREEN UP (E H) EXPORT ACTIVE ENERGY NAME OF THE BUTTON DISPLAYED MEASUREMENT SCREEN UP (E H) IMPORT REACTIVE ENERGY NAME OF THE BUTTON DISPLAYED MEASUREMENT SCREEN UP (E H) EXPORT REACTIVE ENERGY 24
NAME OF THE BUTTON DISPLAYED MEASUREMENT SCREEN UP (E H) APPARENT ENERGY NAME OF THE BUTTON DISPLAYED MEASUREMENT SCREEN UP (E H) T1 TARIFF ENERGY NAME OF THE BUTTON DISPLAYED MEASUREMENT SCREEN UP (E H) GENERATOR ENERGY NAME OF THE BUTTON DISPLAYED MEASUREMENT SCREEN UP (E H) TIME 25
NAME OF THE BUTTON DISPLAYED MEASUREMENT SCREEN UP (E H) DATE Minimum, Maximum and Demand Screens Please, first select the related screen by V I F button in order to see the minimum and maximum values of current and voltage. Then, push SET button and you can see the related screens of MAX/MIN DEMAND.
NAME OF THE BUTTON DISPLAYED MEASUREMENT SCREEN SET (MAX/MIN) MAX(PHASE-PHASE VOLTAGE) NAME OF THE BUTTON DISPLAYED MEASUREMENT SCREEN SET (MAX/MIN) MIN(PHASE-PHASE VOLTAGE) NAME OF THE BUTTON DISPLAYED MEASUREMENT SCREEN SET (MAX/MIN) CURRENT DEMAND NAME OF THE BUTTON DISPLAYED MEASUREMENT SCREEN SET (MAX/MIN) MAXIMUM CURRENT DEMAND 27
NAME OF THE BUTTON DISPLAYED MEASUREMENT SCREEN SET (MAX/MIN) MAXIMUM CURRENT NAME OF THE BUTTON DISPLAYED MEASUREMENT SCREEN SET (MAX/MIN) MINIMUM CURRENT Please, first select the related screen by the P PF button in order to see the minimum, maximum and demand values of the power values. Then, push SET button and you can access the related screens of MAX/MIN DEMAND.
NAME OF THE BUTTON DISPLAYED MEASUREMENT SCREEN SET (MAX/MIN) MAXIMUM ACTIVE POWER DEMAND NAME OF THE BUTTON DISPLAYED MEASUREMENT SCREEN SET (MAX/MIN) MAXIMUM ACTIVE POWER NAME OF THE BUTTON DISPLAYED MEASUREMENT SCREEN SET (MAX/MIN) MINIMUM ACTIVE POWER NAME OF THE BUTTON DISPLAYED MEASUREMENT SCREEN SET (MAX/MIN) MAXIMUM REACTIVE POWER 29
NAME OF THE BUTTON DISPLAYED MEASUREMENT SCREEN SET (MAX/MIN) MINIMUM REACTIVE POWER NAME OF THE BUTTON DISPLAYED MEASUREMENT SCREEN SET (MAX/MIN) APPARENT POWER DEMAND NAME OF THE BUTTON DISPLAYED MEASUREMENT SCREEN SET (MAX/MIN) MAXIMUM APPARENT POWER DEMAND NAME OF THE BUTTON DISPLAYED MEASUREMENT SCREEN SET (MAX/MIN) MAXIMUM APPARENT POWER 30
NAME OF THE BUTTON DISPLAYED MEASUREMENT SCREEN SET (MAX/MIN) MINIMUM APPARENT POWER Settings Screen Access to the Programming Menu: The password input screen is displayed if the SET button of the device is pushed for 3 seconds. When, the correct programming menu password is entered, the programming menus are accessed. Factory default device menu password is 1234.
Mains Connection Type Setting 1. Please, select one of the system connection types from 3F4T, 3F3T, ARON, 3F4T Balanced or 3F3T Balanced by means of the down and up arrow buttons. 2. 3F4T and 3F3T types should be preferred for imbalanced systems. 3. Switch to the next setting by the SET button. Voltage Transformer Presence Setting 1. By means of the down and up arrow buttons, determine whether there is any voltage transformer connected to the system by using Active and Passive options. 2.
Voltage Transformer Primary Setting 1. Adjust the desired primary voltage value from 50 to 400.000 by using the down and up arrow buttons. 2. You can use the SET button for switching between the digits. 3. Switch to the next setting by the SET button after adjusting the desired value. Current Transformer Secondary Setting 1. Select the secondary value of current transformer from 1A or 5A values by using the down and up arrow buttons. 2.
Nominal Frequency Setting 1. Please, select the nominal operating frequency of the device as 50 Hz or 60 Hz. 2. Switch to the next setting by the SET button after adjusting the desired value. Nominal Operating Voltage Setting 1. The nominal operating voltage of the device can be selected from 25V to 300V. 2. You can use the SET button for switching between the digits. 3. Switch to the next setting by the SET button after adjusting the desired value. Time Zone Setting 1.
1. Please, use the SET, down and up arrow buttons for setting the date. 2. You can use the SET button for switching between the digits. 3. Switch to the next setting by the SET button after adjusting the desired value. Time Setting 1. Please, use the SET, down and up arrow buttons for setting the time. 2. You can use the SET button for switching between the digits. 3. Switch to the next setting by the SET button after adjusting the desired value.
There are three different options for the display backlight setting: 1. Always open, 2. Always closed, 3. Automatic When, the automatic option is selected, the backlight turns off almost 3 minutes after any button is pushed. 1. Push set button by selecting the Backlight tab in the Settings, Display menu. 2. The current backlight selection begins flashing. Select one of the options above and push SET button. 3. Do not forget to save the adjusted settings before leaving the menu by means of the BACK button.
The phases of this process: 1. Push the SET button while you are on the clock screen. 2. Push the SET button on the Time Settings screen which is the first displayed screen of the menu. 3. In this section, the clock section begins flashing. 4. Adjust the desired time value by using the down and up arrow buttons. 5. Adjust the minute and second sections to the desired values by switching with the SET button. 6.
2. The chosen Time Zone is displayed on the screen. 3. Enter the menu by pushing the SET button. 4. You can determine the time zone of the desired region in half hours by using the down and up arrow buttons. 5. Push the SET button after completing your selections. 6. Do not forget to save the adjusted settings before leaving the menu by means of the BACK button. Summer Time Mode Setting 1. Push the SET button while you are on the Summer Time mode screen. 2. The Summer Time screen is displayed. 3.
RS-485 Bit Rate Setting The RS-485 communication rate of the device can be adjusted one of the following values: 1. 2. 3. 4. 5. 6. 7. 2400 baud 4800 baud 9600 baud 19200 baud 38400 baud 57600 baud 115200 baud 1. For this process, please push the SET button while you are in the RS-485 bit rate menu. 2. Switch to the selection phase by means of the SET button while you are on the displayed selection screen. 3. Adjust the desired value by using the down and up arrow buttons. 4.
Input Parameter Settings One of the following values can be selected for the input type of the device. 1. Digital input: If, this type is selected, the device senses the logic level of the input. 2. Generator input: If, this type is selected, the device can apply the energy registry to the generator registers according to the input data. 1. For this process, please push the SET button while you are in the Input menu. 2.
3. Output according to the remote selection. In this option, the user can set the output of the device as logic-0 or logic-1 in accordance with the RS-485 protocol. By this way, the user can remotely turn on/off any circuit. 1. For this process, please push the SET button while you are in the Output menu. 2. Switch to the selection phase by means of the SET button while you are on the displayed selection screen. 3. Adjust the desired value by using the down and up arrow buttons. 4.
2. 3. 4. 5. 6. 7. 10 Wh 100 Wh 1 kWh 10 kWh 100 kWh 1 MWh. Pulse output according to Reactive Energy 1. Push the SET button while the PuLS O-1 PArA is selected on the screen. 2. Choose the energy value according to the desired section which the device generates an output pulse as indicated in the screens above. 3. Exit from the menu after completing your selection. 4. Do not forget to save your settings before leaving the menu by means of the BACK button.
1. Push the SET button while the PulS dUrAtIon is selected on the screen. 2. Select the pulse width to be generated by the device in 0.01 second steps as shown in the screen above. 3. Exit from the menu after completing your selection. 4. Do not forget to save your settings before leaving the menu by means of the BACK button. Pulse Duty Factor Adjustment for Pulse Output In this section, the time that the pulse will stay at the logic-1 level is set. 1.
1. Push the SET button while the HoUr CoUn PArA is selected on the screen. 2. Select the parameter where the time counter will start. 3. Switch to the next setting by the SET button after making your choice. Then, the level which this selected parameter will start the time counter is exceeded is determined. 1. As it is seen above, while the level screen of the selected parameter is chosen, push the SET button. 2. Enter the appropriate level value digit by digit.
2. If, SET button is pushed while, you are in the Alarm Enable screen, you can select it as enable or disable by the down and up arrow buttons. 3. Push the SET button after making your choice. 4. Do not forget to save your settings before leaving the menu by means of the BACK button. Selecting Alarm Parameters Follow the steps below for selecting alarm parameters: 1. Push SET while your are in the Setup Alarm menu. 2. Switch to the Alarm parameters screen by pushing the down button. 3.
Alarm Operating Method Settings 1. Push the SET button for selecting the alarm operation method. 2. In this mode, select one of the following options: a. In the window b. Out of the window c. Greater than the value d. Smaller than the value 3. When, in and out of the window are selected, the low and high threshold levels are set. 4. The high threshold level is set for the greater than value option while the low threshold level is set for smaller than the value option is selected. 5.
4. You can save alarm parameters separately for 4 different alarms. 5. Do not forget to save your settings before leaving the menu by means of the BACK button. Hysteresis Setting of the Alarm In this mode, the hysteresis value required for defining an alarm is set. This setting is done in order to prevent that the device does not continuously turns into alarm mode in little changes around the threshold level.
Reset Settings It is possible for the users to reset the minimum, maximum, demand and incident logs saved in the device. Resetting the maximum logs 1. Select the maximum logs from the Reset menu and push the SET button. 2. Select the "Yes" option for deleting by using the down and up arrow buttons in the "Reset Maximum" section shown on the screen. 3. Finalize your input by the SET button. 4. Do not forget to save your settings before leaving the menu by means of the BACK button.
Resetting the Maximum Demand logs 1. Select the max demand logs from the Reset menu and push the SET button. 2. Select the "Yes" option for deleting by using the down and up arrow buttons in the "Reset Max Demand" section shown on the screen. 3. Finalize your input by the SET button. 4. Do not forget to save your settings before leaving the menu by means of the BACK button. Resetting the energy logs 1. Select the energy logs from the Reset menu and push the SET button. 2.
Resetting the time counter 1. Select "Time Counter" logs from the Reset menu and push the SET button. 2. Select the "Yes" option for deleting by using the down and up arrow buttons in the "Reset Time Counter" section shown on the screen. 3. Finalize your input by the SET button. 4. Do not forget to save your settings before leaving the menu by means of the BACK button.
1. 2. 3. 4. 5. 6. 7. 8. 9. Push the SET button in the "Change Pin" screen of the system menu. Enter the previous 4-digit PIN code by using the down and up arrow buttons. If, you enter the wrong code, the "WRONG" warning is displayed on the screen. If, the WRONG warning is displayed, please reenter the pin code by pushing the SET button again. If, you enter the Pin code correctly, the "Change Pin" notice is displayed. In this case, determine the new 4-digit pin code and push the SET button.
Displaying the Serial Number of the Device. 1. Push the SET button while you are on the "System Serial No screen. 2. The 8-digit serial number of the device is displayed on the screen with "Serial No" notice.
The incidents are listed in time sequence. The first log is listed as the newest report while the 255th log is listed as the oldest one. By pushing the SET button you can respectively display the log's; 1. 2. 3. 4. 5. 6. 7. 8. Start date, Start time, End date, End time, Duration, Parameter, Source of the alarm, Value of the alarm. If, no button is pushed for 60 seconds, the system turns back to the measurement screens by leaving the incidents screen.
TECHNICAL INFORMATION AND ATTACHMENTS Technical Information Technical properties Value Dimensions DIN 4 Display LCD Voltage measurement range 10~300 VAC(VLN) Measurement range with transformer 10~999 kV Accuracy %0.5 +/- 1 digit Input Impedance 1.8 MΩ Burden (Input Load) < 0.5 VA Current measurement accuracy %0.
IEC 61557-12 Properties CONFORMITY IEC 61557-12 Edition 2 PMD SPECIFICATIONS Examples of possible specification values Other additional specifications / / PMD Classification SD / Setpoint K55 / / / 0,5 / Type of Specification Supply quality evaluation function (option) Humidity + Altitude Operating performance class for active power or active energy (if function availible) Operating performance class, Symbol for Measurement functions range Other additional according to CEU 61557-12 speci
Compliance with the Standards Standard Year Title IEC 6155712 2008 Electrical safety in low voltage distribution systems up to 1kV (a.a.) and 1,5kV DC(d.a.
EN 550162-1 2009 Specification for radio disturbance and immunity measuring apparatus and methods - Chapter 2-1: Methods of measurement of disturbances and immunity - Conducted disturbance measurements EN 600682-2 2008 Basic environmental testing procedures Part 2:tests-Test B: Dry heat EN 600682-6 2007 Environment test - Chapter 2-6: Tests - Fc tests: Vibration (sinus formed) EN 600682-30 2008 Environmental testing -- Part 2-30: Tests - test db: Damp heat, cyclic (12 h + 12 h cycle) EN 600682-3
Measurement Menu Map 1 59
Measurement Menu Map 2 60
Program Menu Map 61