Instructions
10
Terminal Structure
1) 185 - 300 VAC/VDC Supply Input 3 terminal connections (2 pins)
2) Current measuring input terminal block (6 pins): L1 L2 L3 ve N
3) Voltage measuring input terminal block (4 pins): L1 L2 L3 and N
4) RS-485 terminal block (2 pins)
5) Digital Input/Output terminal (4 pins)
INSTALLATION
The device has shunts for current measurement element there for it must be used with external current
transformers.If the device will be use with other analysers on the same panel ,it is recommented that the
device will be the last point on the current measurement line.
Device has 5 different connection configurations. These configurations are explained with diagrams
below:
3P4W (3 Phase with Neutral) Connection
For this configuration, four voltage connections (including neutral line) and three current connections are
used. Voltage inputs should be connected with 100 mA fuses as shown below.