Owner manual

MAC 10
®
IQ
Fan Filter Unit
14 Innovators in Clean Air Technology | www.envirco.com | Operation & Maintenance
Installation & Service Manual
Cleaning the IQ Pre-filter (foam)
Tools Required: None.
Note: To keep the lter in top operating condition, washing
the foam prelter is recommended every three to six months.
Step 1. To gain access to the prelter, remove the ceiling
panel next to the unit, if applicable.
Step 2. Switch the ON-OFF switch to the off position.
Step 3. Remove the 16”x23” prelter from the snap-in frame. (See Figure)
Step 4. Clean the prelter by hand washing in water with a mild detergent or by using a vacuum cleaner. Allow prelter to
dry completely before replacing.
Step 5. Reassemble by reversing the above steps.
WARNING
DISCONNECT THE UNIT FROM THE ELECTRICAL
POWER SOURCE BEFORE ATTEMPTING
ANY SERVICE
ON/OFF Switch
(foam prelter)
16” x 23”