Operating instructions
FREESTANDING INSTALLATION: 
CHIMNEY
: 
Vent the stove into a clean, lined, approved masonry 
chimney in good condition, conforming to local building 
codes or a listed 6” factory built chimney suitable for 
use with solid fuels and conforming to, ULC-S629 in 
CANADA or UL-103HT in the U.S.A.. Connect the stove 
to this chimney with a short and straight 6” (150 mm), 
25 gauge or heavier, single wall black or blued steel 
smoke pipe. Connection to all masonry chimneys must 
be a metal or masonry thimble cemented in place. All 
smoke pipes must slope upwards, all connections must 
be tight and secured with three sheet metal screws 
equally spaced. The smoke pipe length should not 
exceed 40% of the chimney height above the stove. 
A non-combustible floor protector is required 
under all freestanding units. The floor 
protection must extend 18” (457 mm) in front of 
the unit and 8” (203 mm) to each side. When 
venting into a masonry chimney the floor 
protector must be installed directly below the 
chimney vent and 2” (50.8 mm) on either side 
of the chimney vent
. 
DO NOT CONNECT THIS UNIT TO A CHIMNEY 
FLUE SERVING ANOTHER APPLIANCE.
MAINTAIN THESE MINIMUM CLEARANCES TO UNSHIELDED COMBUSTIBLES*
DOUBLE WALL 
PIPE** 
DOUBLE WALL 
PIPE** 
  MODEL 1000  MODEL 1600  MODEL 2100  MODEL 1000  MODEL 1600 
A. SIDE TO UNIT  19 “ (485 MM)  20” (510 MM)  22” (560 MM)  14” (355 MM)  11” (280 MM) 
B. REAR TO UNIT  10” (2556 MM)  12” (300 MM)  12” (300 MM)  6” (150 MM)  4” (101 MM) 
C. CORNER TO UNIT  6” (150 MM)  6” (150 MM)  8” (200 MM)  2” (50 MM)  6” (150 MM) 
D. SIDE TO COLLAR  28” (710 MM)  29” (735 MM)  31” (790 MM)  23’ (585 MM)  20” (508 MM) 
E. REAR TO COLLAR  13” (330 MM)  16.5” (420 MM)  16.5” (420 MM)  9” ( 230 MM)  8.25” (210 MM) 
F. CORNER TO COLLAR  16” (405 MM)  16.5” (420 MM)  19 “ (485 MM)  11.5” (290 MM)  15.5” (394 MM) 
CAUTION: AN UN INSULATED SMOKE PIPE MUST NOT PASS THROUGH AN ATTIC, ROOF SPACE, 
CLOSET OR SIMILAR CONCEALED SPACE, OR THROUGH A FLOOR, CEILING, WALL, OR PARTITION, 
OR ANY COMBUSTIBLE CONSTRUCTION. 
*ALL CLEARANCES CAN BE REDUCED WITH SHIELDING ACCEPTABLE TO THE LOCAL AUTHORITY. 
**DOUBLE WALL: IN CANADA:
 ANY ULC-629 LISTED CHIMNEY SYSTEM WITH THE ACCOMPANYING 
LISTED DOUBLE WALL VENT CONNECTOR. 
IN U.S.A.: ANY HT-103 LISTED CHIMNEY SYSTEM WITH THE ACCOMPANYING 
LISTED DOUBLE WALL VENT CONNECTOR.
11