Operating instructions

MOBILE HOME INSTALLATION
SPECIAL REQUIREMENTS: Pedestal models 1000 and 1600 are approved for mobile homes. All freestanding
installation requirements on the preceding page plus the following must be met:
VENTING:
In Canada: Any ULC-629 listed chimney system with the accompanying double wall vent connector. In U.S.A.
Any HT-103 listed chimney system with the accompanying double wall vent connector. Do not connect a listed
chimney of one manufacture with a listed double wall connector from another manufacture. These connectors
must be installed in accordance with the manufacturer’s instructions. Use only specified components. The
chimney and pipe must extend at least 10-ft. (2.4m) above the stove and 3-ft. (.9 m) above the highest point of the
roof. (RECOMMENDED CHIMNEY HEIGHT 12’ FEET) Install a rain cap with spark arrestor at the top that will not
impede the smoke exhaust. The chimney must be supported at the ceiling or roof so that its weight will not sit on
the stove. Seal with silicone to maintain vapor barrier at the chimney and outside air penetrations. CAUTION:
THE STRUCTURAL INTEGRITY OF THE MOBILE HOME FLOOR, WALL, AND CEILING/ROOF MUST BE
MAINTAINED.
OUTSIDE AIR :
Connection from the stoves air intake to the outside
is mandatory
, (MOBILE HOMES ONLY) either
through a hole in the wall not higher than the stoves
bottom, or through a hole in the floor beneath the
pedestal using the fresh air adapter provided. If the
air intake is through the floor, the hole in the pedestal
back must be closed with the sheet metal cover
provided. Avoid cutting any floor joists, wall studs,
electrical wiring or plumbing. Seal around the outside
air pipe with insulation to prevent drafts. Also install a
¼” mesh rodent or pest screen in the end of fresh air
pipe. Fresh air connection must be of a non-
combustible material (example: 4” 10.16 cm flexible
aluminum single wall pipe.)
Fresh air could also be supplied from a vented
crawlspace
The pedestal must be firmly bolted to the floor using
¼” bolts. Be sure to replace any insulation or panels
removed when fastening the bottom nuts.
If room air starvation occurs because the air intake is
blocked with ice, leaves etc. Or because the stove
door was left open, or due to a strong exhaust fan
operating, dangerous fumes could be sucked into the
room.
IN SOME AREAS IT MAY BE REQUIRED TO ELECTRICALLY GROUND THE STOVE.
When this unit is installed in a Mobile Home it must be grounded to the steel chassis or connected to a grounding
rod.
Manufactured (Mobile) home installation must be in accordance with the Manufactured Home Construction and
Safety Standard, UL 307B, Title 24 CFR, Part 3280 and/or The Standard for Manufactured Home Installations,
ANSI A225.1/NFPA 501A
WARNING: DO NOT INSTALL IN A MOBILE HOME SLEEPING ROOM.
13