Owner`s manual

16
DV Shown
BV Shown
DV Only: Maximum height allowed for the vent is 35ft
(10.67m).
Install sealed throat connector or flashing to prevent
leakage of room air up through chimney.
DV Only: Before installing vent liners, mark each liner on
both ends to designate which is the intake and the
exhaust.
Measure the height of the chimney beforehand and
purchase the appropriate kit. Never attempt to over-
stretch a flexible liner t
o accommodate the height of the
chimney.
The flue damper can be fully blocked open or removed for
installation of the Sienna; the smoke shelves, shields and
baffles may be removed if attached by mechanical
fasteners.
The chimney must be clean, in good working order and
constructed of non-combustible materials.
Make sure that all chimney cleanouts are tight fitting and
will not permit air to leak into the chimney.
R
efractory, glass doors, screen rails, screen mesh and
log grates can be removed from the fireplace before
installing the Sienna.
Initial Installation
QUALIFIED INSTALLERS ONLY
Venting fiRePLace inseRts:
TheENVIRO SIENNAmaybeinstalledandventedintoanysolidfuelreplacethathasbeeninstalled
inaccordancewiththeNational,Provincial/Stateandlocalbuildingcodesandhasbeenconstructedof
non-combustiblematerials.Thisappliancemustnotbeconnectedtoachimneyueservingaseparate
solidfuel-burningappliance. Beforestartingreferto InItIal InstallatIon - preparIng your sIenna For
InstallatIonand InItIal InstallatIon - conVertIng a DIrect Vent FIreplace to a b-Vent FIreplace.
Anapprovedchimneylinerandraincapmustbeused.Athroatconnectororashingmust beinstalled
to ensure a tight seal, top performance, safety and efciency. Carefully follow the manufacturer’s
instructions that accompany the chimney liner kit. Use listed B-Vent or Flexmaster double walled
aluminumexvent.
Ifnecessary,removetheventcollarplatefromthetopoftheinsertandconnectitsecurelytotheliner
withsheetmetalscrewsand/orhoseclamps.Checkforanytearsinthelineratthispoint.IMPORTANT:
Thescrewsthatholdtheventcollarplateinitsapprovedpositionmustbeinstalled.
Provideforproperandadequateventingandairsupplyforthisapplianceinaccordancewiththetables
inthecurrentNationalFuelGasCode,Z223.1/NFPA54ortheCSAB149.1.
Theowofcombustionandventilationairmustnotbeobstructed.
Means for inspection of the vent connection to the appliance at the time of installation shall be
provided.
Figure 20: Installation of Sienna DV and BV.