Owner`s manual

NOTE: IftheSiennaunitispulled
outofitsinstallation,andthevent
airintakesystemisdisconnected
for any reason, ensure that the
vent-airintakepipesarere-sealed
with high-temperature sealant
or silicone and reconnected with
three (3) sheet metal screws
evenlyspaced.
IMPORTANT:TheSiennaistobe
vented only with vertical venting
–nohorizontal.
2ft (0.6m)
Minimum
3ft (0.9m)
Minimum
Within
10ft (3m)
Roof ridge or
any other portion
of a building
Figure 21: Roof Clearances.
Table 3: Vent termination clearances
Minimum Clearance Description
3ft(0.9m)
Clearanceabovethehighestpointwhereitpassesthrougharoofsurface,refer
toFigure21.
24in(0.6m)
Clearanceabovearoofridge,anyotherportionofabuilding,oranyotherob-
structionwithinahorizontaldistanceof10feet(3m),refertoFigure21.
5ft(1.5m)
Clearanceforaventorchimneyaboveeitherthehighestconnectedappliance
drafthoodoutlet,oruecollar.
6ft(1.83m) Clearancetomechanicalairsupplyinlet.
3ft(0.9m) Clearancetoeachsideofcenterlineextendedabovemeter/regulatorassembly.
6ft(1.83m) Radialclearancearoundserviceregulatorventoutlet.
12in(30cm) Clearanceabovegrade,verandah,porch,deck,orbalcony.
3ft(0.9m)
Clearancetoabuildingopeningorcombustionairinletofanotherappliance,
exceptwiththeapprovaloftheauthorityhavingjurisdictionforthefollowing
reducedclearances.
9in(0.23m) Exceptionforinputsuptoandincluding50,000Btu/h(15kW)
12in(0.3m)
Exceptionforinputsexceeding50,000Btu/h(15kW)butnotexceeding100,000
Btu/h(30kW)
zeRo cLeaRance fiRePLace instaLLation:
ThemetalooroftheZCsolidfuelreboxcanberemovedtoallowtheinstallationoftheinsert.THE
CLEARANCETOCOMBUSTIBLEMATERIAL UNDERTHEINSERTIS ½”(13mm). YOUMUST USE THE
LEVELINGLEGSTORAISETHEINSERTAMINIMUMOF½”(13mm)IFTHEUNITISTOBEINSTALLED
ONCOMBUSTIBLEMATERIAL.Thesidewallsandtopstructureofthesolidfuelreboxcannotbealtered
with the exception of removable dampers and bafes. THE ORIGINAL FIREPLACE MAY NEVER BE
RETURNEDTOSOLIDFUELUSEINTHISCONDITION.
IMPORTANT:Ifthefactory-builtreplacehasnogasaccesshole(s)provided,anaccessholeof1.5inch
(37.5mm)orlessmaybedrilledthroughthelowersidesorbottomofthereboxinaproperworkmanship
likemanner.Thisaccessholemustbepluggedwithnon-combustibleinsulationafterthegassupplyline
hasbeeninstalled.Cuttinganysheet-metalpartsofthereplace,inwhichthegasreplaceinsertisto
beinstalled,exceptastestedfortheoorisprohibited.
Initial Installation
QUALIFIED INSTALLERS ONLY
17