Owner`s manual

Initial Installation
QUALIFIED INSTALLERS ONLY
VERTICAL TERMINATION:
attic rafters. See end of this section. Do not pack air
spaces with insulation.
Step 2. Set the replace in the desired location. Drop a plumb
bob down from the ceiling to the ue exit. Mark the
location where the vent will penetrate the ceiling and
drill a small hole at this point. Next, drop a plumb
bob from the roof to the hole drilled in the ceiling.
Mark the spot where the vent will pass through the
roof. Determine if the ceiling joists, rafters or other
framing members will obstruct the venting system.
The replace may need to be relocated to avoid
cutting any load bearing members or an offset elbow
can be used.
Step 3. To install the wall thimble in a at ceiling, cut a 10in
(25.4cm) x 10in (25.4cm) x 10in square hole in the
ceiling. The previously drilled hole should be at the
center of the new hole. The square hole should be
framed. See Figure 17.
Step 4. Assemble the desired lengths of pipe and elbows
necessary to reach through the square hole from
the replace adapter. Ensure all the pipe and elbow
connections are fully twisted and locked together.
Step 5. Cut a 10in (25.4cm) x 10in (25.4cm) hole in the roof,
centered on the small hole cut previously. Continue to
assemble lengths of pipe necessary to reach from the
ceiling support box up through the roof line.
NOTES:
1. Horizontal pipes must not be level. For every 12in (30cm) of horizontal travel (away from the stove),
there should be at least 1/4in (6mm) of vertical travel. Never allow the vent to run downward, as
this could cause high temperatures or even present the possibility of a re.
2. The exterior of the horizontal vent termination must not be blocked or obstructed.
3. If the vent termination is not being attached to wood, the four wood screws provided should be replaced with
material appropriate fasteners.
4. For buildings with vinyl siding, a vinyl standoff should be installed between the vent cap and the exterior wall.
Attach the vinyl siding standoff to the horizontal termination. Note that the termination bolts onto the at portion
of the standoff, providing an air space between the wall and the vent termination. The air gap prevents excessive
heat from possibly melting the vinyl siding.
5. Horizontal pipes must be supported every 3ft. Plumber’s all round strap will sufce.
6. When running horizontal pipe, clearances to combustibles must be maintained (1in (3.8cm) sides, 1” (3.8cm)
bottom, and 2” (5.1cm) top)
pipe support
strap
Figure 21. Vertical Vent Termination
18
Step 1. Check required clearances to combustibles when passing through ceilings, walls, roofs, enclosures, or