masonrY Fireplace installation:
Unless you are experienced, we recommend installation by your dealer or a 
professional installer.
Install only in a masonry replace with a good-condition chimney at least 15 ft (4.6 m) high, both of 
which have been constructed in accordance with the building code. Refer to Tables 4 and 7 for minimum 
masonry replace dimensions. Be sure the replace and chimney are clean and sound without any cracks 
or loose mortar. Do not remove any bricks or mortar from the replace.
If there is a combustible oor in front of the 
masonry replace, the replace insert must 
be 8”  (203 mm) above the  combustible 
oor, and oor protection must be provided 
18” (457 mm) in front of the replace insert 
and 8” (203 mm) to each side of the unit. 
Refer  also  to  sPecifications  -  cLearances  to 
coMbustibLes - 1200-c insert and sPecifications 
- cLearances to coMbustibLes - 1700-c insert.
1. Remove any replace damper or fasten 
in a permanent open position.
2. (IN CANADA) The stove is vented with 
a 6” stainless steel liner that goes directly to 
the top of the chimney and is covered with 
a rain cap. The chimney top is sealed with 
a  ashing  or  steel  plate  that  supports  the 
weight of the chimney liner. The installation 
must conform to the liner’s manufacturer’s 
instructions.
This  replace  must  be  installed  with  a 
continuous  liner  of  6”  diameter  (CANADA 
ONLY)  extending  from  the  replace 
insert  to  the  top  of  the  chimney.  The 
chimney liner must conform to the Class 3 
requirements of  CAN/ULC-S635  Standard 
for Lining Systems for Existing Masonry or 
Factory-Built Chimneys and Vents, or CAN/
ULC-S640  Standard  for  Lining  Systems  for 
New Masonry Chimneys.
(IN  U.S.A.)The  appliance  when  installed, 
must follow local  building codes, in the 
absence  of  local  building  codes,  with  the 
current  NFPA  211  Standard  for  Chimneys, 
Fireplaces,  Vents,  and  Solid  Fuel-Burning 
Appliances.
Figure 10: Insert Installation into existing replace with 
hearth.
16
Floor
Protection
Combustible Floor
Masonry Fireplace
 8"
(203 mm)
Rain Cap
Steel Plate or Flashing
Flexible or Rigid 6"
Stainless Steel Liner
Mantel
Top Facing
Damper Removed
or Fastened Open
Sheet Metal Screws
Fastening Collar to
Stainless Steel Liner
Surround Panel
USA 16” (406 mm)
CND 18” (450 mm)