KES Enviro Engineering Manual Table of Contents Introduction KES Enviro Unit Principle of Operation KES Enviro Filter Unit (KES-ISH) KESF Enviro Fan Unit Indoor Vertical Units Fan Arrangements Fan Installation in Fire Compartments KES-ISH Enviro Box Controls KES Selection Sample Specification Electrical Wiring Diagrams KES-ISH Indoor Filter Box KESF Indoor Fan Unit (DWDI and Odor Spray) KESF Indoor Fan Unit (SWSI Fan) KESF Outdoor Fan Unit (DWDI and Odor Spray) KESF Outdoor Complete Unit KESF Indoor Vertica
1 KES Enviro Engineering Manual INTRODUCTION The SPRING AIR SYSTEMS INC. Kitchen Enviro System (KES) has been designed and constructed specifically for a commercial kitchen exhaust. The units are simple to operate and easy to maintain. The individual components have been selected to provide trouble free, reliable operation.
2 The KES unit is installed to clean the exhaust air of grease and odor. The UL/ULC listing allows the exhaust to be discharged at low levels. In other words the exhaust ductwork may be discharged through side exterior walls below the roof level. These exceptions to the standard NFPA-96 code are possible with a combination high efficiency filtration system and a unique electrical and mechanical safety circuit.
3 Within the KES Enviro Filter Unit (KES-ISH) the exhaust air travels through three stages of particulate filters. 1.Two (2) inch (51 mm) pleated - 30% ASHRAE 52-76 filters 2.Twenty-one (21) in. (525 mm) bag - 90% ASHRAE 52-76 filters 3.Twelve (12) in. (305 mm) box - 95% DOP filters, (99% ASHRAE 52-76) Within the KES Enviro Filter Unit (KES-ISH) the exhaust air is cleaned of airborne grease, lint and dirt particulate.
4 KES ENVIRO FILTER UNIT (KES-ISH) The KES Enviro Filter unit contains the LV10 panel, pressure switches, and three stages of filters. The unit is constructed of 16 gauge steel inner shell, continuously welded and liquid tight in accordance with the NFPA-96. The outside of the unit is wrapped in 1.5” insulation and 18 gauge steel protective covering primed and painted. Channels running along the length of each side support the unit.
5 Every KESF unit is equipped with a backward Inclined; AMCA rated, Class II, exhaust fan with heavy-duty bearings, and two groove sheaves. The following options are also available: The KESF fan unit is always internally isolated. The KESF fan unit has spring mounted isolators inside the KESF fan unit and does not require any external flexible connection outside the unit. The KESF fan unit has a Class II: The Class of the fan is dependent on the total static pressure and CFM of the system.
6 minutes for a preset spray time. Both the cycle time and the length of spray are adjustable. The time setting relates to the type of cooking and appliances under the hood. See Figure 7. S P R A Y 4 .0 0 C U T H O L E IN 4 IN C H E S IN A L O N G W ID T T O P O F S P R A E D H Y X H A U S T D U C T IA M E T E R , C E N T E R E D A N D 4 IN C H E S F R O M E N C L O S U R E 2 2 .0 0 E L E C T R IC A L A N D S P R A Y C O M P O N E N T S L O C A T E D IN S ID E S P R A Y E N C L O S U R E 7 .
7 INDOOR VERTICAL UNITS Indoor, vertical units are also available for exhaust volumes up to and including 10,000 CFM. The unit is generally located beside the hood or in a mechanical room on the floor.
8 FAN ARRANGEMENTS INDOOR/HORIZONTAL/SUPPORTED INDOOR/VERTICAL/SUPPORTED TOATMOSPHERE INDOOR/HORIZONTAL/SUSPENDED OUTDOOR/ROOFMOUNTED INDOORFILTER/OUTDOORFAN INDOORFILTERBOXES/OUTDOORFAN Typical KES-ISH Filter Box and KESF Fan Arrangements Figure 10 _____________________________________________________________________________ Spring Air System Enviro Engineering Manual 01/038
9 FAN INSTALLATION IN FIRE COMPARTMENTS FIRERATEDCOMPARTMENT#2 FIRERATEDCOMPARTMENT#2 FIRERATEDENCLOSURE FIRERATEDSEPARATION FIRERATEDCOMPARTMENT#1 FIRERATEDSEPARATION FINISHEDCEILING FINISHEDCEILING FIRERATEDCOMPARTMENT#1 UNITINSTALLEDOUTSIDEOFFIRECOMPARTMENT VERTICALUNITINSTALLINFIRECOMPARTMENT FIRERATEDCOMPARTMENT#2 FIRERATEDCOMPARTMENT#2 FIRERATEDSEPARATION FIRERATEDSEPARATION FIRERATEDENCLOSUREEQUALTOFINISHEDCEILING FINISHEDCEILING FIRERATEDCOMPARTMENT#1 HORIZONTALUNITINSTALLINFIRECOMPAR
10 KES-ISH ENVIRO BOX CONTROLS LV10 J-Box The main Enviro Unit interlocks from the remote panels is the LV10 J-Box located on the KES Enviro Filter Box (KES-ISH). The LV10 j-box is located on the same side of the KES-ISH as the filter access and toward the exhaust inlet end.
11 NORMAL: Exhaust airflow is normal and the unit is functioning properly. FIRE: There is a temperature in excess of 225 F in the KES-ISH inlet. The unit will shut off completely. PANEL MOUNTING HOLES LOCATED IN PANEL BACK. 5" 8.0" FILTER OVERIDE NORMAL WARNING FIRE PREFILTER CLOGGED BOX FILTER 14" CLOGGED BAG FILTER CLOGGED FILTER REMOVED PRE FILTER CLOGGED: Operation will stop. The 2” deep pre-filter located in the KES-ISH filter unit is plugged and must be replaced.
12 The remote annunciation panel RPD10 is located in the kitchen near the water wash control for annunciation of the following conditions: NORMAL: Exhaust airflow is normal and the unit is functioning properly. FIRE: PANEL MOUNTING There is a temperature in excess of 225 F in HOLES LOCATED 5" the KES-ISH inlet. The unit will shut off IN PANEL BACK. completely. KES ON/OFF FILTER OVERIDE NORMAL PRE FILTER CLOGGED: Operation will stop.
13 SLAB KES20-18-ISH ENVIRO FILTER UNIT KESF20-18-IH ENVIRO FAN UNIT 1840 CFM DISCHARGED TO ATMOSPHERE 14 19 13 15 18 FIELD PIPING AND WIRING TO CONFORM TO ALL LOCAL CODES REQUIREMENTS. FINISHED CEILING 6 EXHAUST DUCTWORK FROM HOODS TO KES UNIT TO BE IN ACCORDANCE WITH THE NFPA-96 ALL WELDED LIQUID TIGHT CONSTRUCTION. DRY GREASE EXTRACTOR MODEL DD-B-F-10.0/3.
14 KES SELECTION Two parameters are required to select a KES unit; the total exhaust volume, CFM (l/s) and the external static pressure, inches W.C. (kpa). To minimize the initial capital cost and future operation and maintenance costs the most important consideration is to reduce the total exhaust air volume. Spring Air Systems sales representatives have a KES Enviro selection computer program. Contact your local representative and a selection can be made in minutes.
15 The external static pressure is made up of many components. Here are a few to consider: a)Spring Air Kitchen exhaust hood - typically between 0.5 to 1.5” W.C. (0.13 to 0.33 kpa) Calculated by Spring Air. b)Exhaust inlet ductwork from the hood to the KES-ISH filter box. c)Internal Static Pressure of KES-ISH filter box - typically between 2.0 to 3.5” W.C. (0.50 to 0.88 kpa). Calculated by Spring Air. d)Exhaust ductwork from the KES-ISH filter unit to the KESF fan unit.
16 Sample Selection A hospital cafeteria is expanding the kitchen. An additional SPRING AIR SYSTEMS water wash hood model HF-B 10.4 is to be installed. The cafeteria is located on the first floor of a four-(4) story section of the hospital. The exhaust must discharge at the ground floor level into a courtyard. A SPRING AIR SYSTEMS kitchen enviro system (KES) is required. Water wash hood: CD-B 10/4 Length: 10 ft. Width: 4 ft. Exhaust volume: 3,000 CFM External Static Pressure: 1.26” W.C.
17 Engineering Data Project Name: Item Number: Model Number: Arrangement: Unit Weight: Exhaust Volume: External Static Pressure: Brake Horsepower: Fan Speed: Exhaust Fan Motor: Hi Voltage - FLA: Low Voltage: Remote Panel: Hoods Connected: Item # Model# H-1 CD-B-10/4 - Sample - EF-1 - KES30-30-I-H - indoor / horizontal - 1100 lbs. - 3000 CFM - 1.75" W.C. - 4.66 Hp - 2766 rpm - 5.00 Hp - 208V/3/60 - 15.6 AMPS. - 120V/1/60 - 10 AMPS.
18 Controls: Outdoor Unit The LV10 J-Box, and pressure switches shall be located in a weatherproof enclosure with the motor starter and overload on the KESF fan unit. When the odor spray option is selected this enclosure will have a 300-watt baseboard heater and thermostat in cold climates. The unit shall include a firestat. The LV10 J-BOX shall be interconnected to a RPD10, RPD10A or RPW10 remote panel.
19 Exhaust Fan: The KES unit shall be supplied with a CLASS II, AMCA rated double width, double inlet, (single width, single outlet SWSI) airfoil centrifugal fan statically and dynamically balanced. The fan shall be mounted on a heavy duty turned, ground and polished steel shaft, internally isolated, (externally isolated with hanging isolators shipped loose for field installation). The bearings shall be heavy-duty, prelubricated type. V-belt drives shall be two groove, adjustable up to 7.
20 ELECTRICAL WIRING DIAGRAMS RPW10 ELECTRICAL DATA 1 3 4 15 AMP CURCUIT BREAKER THREE (WIRES) TO THE WATER WASH CONTROL PANEL - 120V/1/60 - 10 AMPS 1 4 OVERIDE SWITCH 5 12 13 14 15 16 17 18 TO KES UNIT LV10 PANEL ON FILTER BOX - TEN (10) WIRES 120V/1/60 - 10 AMPS. POWER WIRING BY GENERAL CONTRACTOR CONTROL WIRING BY MECHANICAL CONTACTOR FACTORY WIRING BY SPRING AIR SYSTEMS L N I1 I2 I3 I4 I5 I6 I7 I8 L N I1 I2 I3 I4 AUX! Mo 09:00 01. 20.
21 Figure 18 KES-ISH INDOOR FILTER BOX 1 .5 0 2 .5 0 A D B H E I 4 .0 0 J C F K G L P L A N V IE W S E C T IO N V IE W KES-ISH . A B C D E F G H I J K L Model No. 10 64 25.5 24.5 22.75 1.38 18 4.75 9 8.25 10 8.5 3 20 64 25.5 32 23 1.25 25 5 18 3.75 10 13.25 3 30 64 37.0 32 34 1.5 25 5 27 5 10 13.25 3 40 67 49.0 32 34 7.5 25 5 30 9.5 12 11.75 3 50 69 49.0 44 34 7.5 25 5 32 8.5 14 17.25 3 50F 69 60.5 32 34 13.
22 KESF INDOOR FAN UNIT DWDI and Odor Spray 4 " T Y P IC A L A D H E F B I C J G 7 .0 0 L K S E C T IO N V IE W P L A N V IE W KESF MODEL A No. B C D E F G H I J K L 10 67 37 32 15.5 10.75 13.5 15.5 23 7 18 5 3 20 67 37 32 15.5 10.75 13.5 15.5 23 7 25 5 3 30 67 37 32 15.5 10.75 13.5 15.25 34 1.5 25 5 3 40 67 49 36 18.5 15.25 16 16.75 34 7.5 25 5 3 50 72 49 44 18.5 15.25 16 16.75 34 7.5 25 5 3 60 72 49 44 22 13.
23 KESF INDOOR FAN UNIT SWSI Fan A EX HA US T O UTL ET D 5 .0 0 1 .5 0 5 .0 0 1 .5 0 G E E B E X H A U S T IN L E T F R O M E N V IR O F IL T E R U N IT F C E X H A U S T IN L E T F R O M E N V IR O F IL T E R U N IT H L P L A N V IE W S E C T IO N V IE W KESF Model No. A B C D E F G H L 10 50 31 48.5 11 15 8 13 21.5 3 20 50 31 50 11 15 8 13 21.5 3 30 50 31 50 11 15 8 13 21.5 3 40 50 31 50 11 15 8 13 21.5 3 50 52 35 55 13 18 9 17.
24 KESF OUTDOOR FAN UNIT DWDI and Odor Spray 1.50 A 4.00 K J D K EXHAUST INLET FROM ENVIRO FILTER UNIT B E 9.00 PLAN VIEW H 5.00 EXHAUST DISCHARGE TO ATMOSHERE 3.00 C F SPRING FRESH EXHAUST INLET FROM ENVIRO FILTER UNIT G L KESF Model A No. B C D E F G H J K L 10 67 37 36 23 7 18 5 13.5 15.5 10.73 3 20 67 37 36 23 7 25 5 13.5 15.5 10.73 3 30 67 37 36 34 1.5 25 5 13.5 15.5 10.73 3 40 67 49 36 34 7.5 25 5 16 18.54 15.
25 KES OUTDOOR COMPLETE UNIT 2.50 A J H D J B E 9.00 K 3.00 F C G L DWDI and Odor Spray KES Model A No. B C D E F G H J K L 10 131 37 43 9 8.25 10 8.5 15.6 10.7 13.5 3 20 131 37 43 18 3.75 10 13.25 15.55 10.73 13.5 3 30 131 37 43 27 5.0 10 13.3 15.6 10.7 13.5 3 40 134 49 43 30 9.5 12 11.75 18.54 15.23 16 3 50 141 49 44 32 8.5 14 17.25 18.54 15.23 16 3 60 141 49 44 34 7.5 16 16.25 21.93 13.
26 KESF INDOOR VERTICAL COMPLETE UNIT DWDI and Odor Spray A D F E J G K B H J 7.0 PLAN VIEW EXHAUST INLET FROM NFPA-96 HOOD 2.5 N M EXHAUST TO ATMOSPHERE 1.5 C 3.0 KES-IV A Model No. B C D E F G H J K M N 10 20 30 40 50 60 80 100 42 42 42 51 51 51 55 66 78 78 78 80 84 84 90 90 23.7 35.73 35.7 36.21 50.21 50.58 62.57 66.38 8.75 8.72 8.75 9.25 11.25 11.5 11.5 15.5 15.55 15.55 15.55 18.54 18.54 21.93 21.93 25.12 13.45 13.45 13.45 15.87 15.87 18.78 18.78 25.12 25.55 26.55 26.
27 KES UNIT WEIGHT CHART (lbs) KES Model Number KES-ISH Filter Box KESF Fan Unit DWDI Odor Pellet Odor Spray KESF Fan KESV Section unit SWSI Vertical unit Section 10 250 630 550 950 200 100 20 300 630 600 1050 300 100 30 350 710 700 1100 450 110 40 450 710 800 1300 500 110 50 550 950 1000 1650 550 150 50F 550 n/a n/a n/a 550 150 60 600 950 1100 1750 600 150 60F 650 n/a n/a n/a 600 150 80 700 1300 1350 2100 900 170 100 850 1600 1500 2550