Unit installation

_____________________________________________________________________________
Spring Air System Enviro Engineering Manual 01/0310
10
KES-ISH ENVIRO BOX CONTROLS
LV10 J-Box
The main Enviro Unit interlocks from the remote panels is the LV10 J-Box located on the KES
Enviro Filter Box (KES-ISH). The LV10 j-box is located on the same side of the KES-ISH as the
filter access and toward the exhaust inlet end.
KES TEL E MOTOR ST ARTER
IN EEMAC12 ENCLOSURE
MOU NTED ON F AN UNIT
95
1
KES F AN /NO RMAL OP ERATI ON
KESF FAN SECTION
30 AMP D I SC ONN ECT
IN EEMAC12 ENCLOSURE
MOU N TED ON F AN U NIT
T1L1
M1
T2
T3
L2
L3
96
G1
KES-ISH FILTER SECTION
____ FL A
____V/3/60
FACTORY WI R ING BY SPRI N G AIR SY STEMS
PO WER WI R I NG BY GEN ER AL CONTRACTOR
POWER SUPPLY
CON TROL WI R I N G BY MEC HANI CAL CONTAC TOR
RESE T
DESCRIPTION
LEGEND
4
1
12
14
13
5
15
16
17
18
5
TERMINAL
1&4 POWER FROM RPD10
13
14
16
17
15
18
BAG FILTER CLOGGED
FIR EST AT - H I GH L I MI T
0DOR SPRAY UNIT
FILTER OUT/LOW AIR
BOX FILTER CLOGGED
LV10 RESET
PREFILTER CLOGGED12
TEN (10) WIRES TO THE
417
L OCAT ED ON KES FAN SECTI ON
EXHAUST FAN MOTOR
____ HP
4.2 AMPS. MAXI MU M. WIRES BY SP RI NG AI R
TO THE ODOUR CONTROL UNIT 120V/1/60
WIRING FR OM EXHAUST FAN MOTOR STARTER
OPTIONAL ODOUR CONTROL PANEL
FILTER REMOVE D SWITCH ES
LV10 J-BOX
LOCATED ON
KES F I L TE R
UNIT
P1
P3
P4
P2
FILTER CLOGGED PRESSURE SWITCHES
P2 - BAG FILTER (SET AT 1.0" W.C.)
P1 - PREFILTER (SET AT 1.0" W.C.)
P3 - BOX F ILTER (SET AT 1.2" W.C.)
P5 - BOX FILTERS (SET AT 0.25" W.C.)
P5
TH1
EXHAUST INL ET SET AT 225 °F
HI T EMP STAT LOCATED IN T HE
P4 - BAG FILTER S (SET AT 0.25" W.C.)
L1
O/L
L2
L3
T1
T3
T2
A1
A2
637
M1
WI RING HAR N ESS I N
MOTOR STARTE R
THREE WIRES FROM LV10 PANEL TO EXHAUST FAN MOTOR STARTER BY
MECH ANICAL WHEN KES F AN AND F I L T ER SECTION S ARE SP L I T 120 V/1 /6 0, 5 AMPS
1
TO REMOTE CONTROL STATION L OCATED IN
RPW10 - 120V/1/60 - 10 AMPS.
IN THE KITCHEN AREA MODEL RPD10 OR
Typical LV10 J-Box for Indoor KES-ISH with Odor Spray
Figure 12
RPW10 Remote Annunciation Panels
Used in conjunction with a Water Wash Ventilator
The KES RPW10 remote control panel activates unit shut down upon any of the conditions listed
below.
1.Operation of the KES-ISH with dirty or clogged pre-filters, bag filters, or box filters.
2.Operation of the KES-ISH with the bag for box filter removed.
3.Low air volume through the KES-ISH.
4.A fire in the KES-ISH inlet
The remote annunciation panel RPW10 is located in the kitchen near the water wash control for
annunciation of the following conditions: