The remote annunciation panel RPD10 is located in the kitchen near the water wash control for
annunciation of the following conditions:
NORMAL:
Exhaust airflow is normal and the unit is functioning properly.
FIRE:
There is a temperature in excess of 225 F in
the KES-ISH inlet. The unit will shut off
completely.
PRE FILTER CLOGGED:
Operation will stop. The 2” deep prefilter
located in the KES-ISH filter unit is plugged
and must be replaced.
BAG FILTERS CLOGGED
Operation will stop. The 22” deep bag filter located in the KES-ISH filter unit is plugged and must
be replaced. Rotate the warning switch and the unit will resume operation. Change filter
immediately after cooking is completed for the day.
BOX FILTERS CLOGGED:
Operation will stop. The 12” deep box located in the KES-ISH filter unit is plugged and must be
replaced. Rotate the warning switch and the unit will resume operation. Change filter immediately
after cooking is completed for the day.
FILTERS REMOVED:
Operation will stop. The bag or box filter has been remove from the KES-ISH filter unit.
Operation will stop until the filters are replace.
WARNING:
The override switch has been switched on. The PRE, BAG, or BOX filter must be replaced
immediately after cooking has ceased for the day.
Override Switch:
Rotating this switch provides approximately 4 hours to change the dirty filter that has
annunciated. Failure to change the dirty filter will cause the complete unit to shutdown.
Unit on/off Switch:
Rotating this switch turns the KES Enviro system on and off.
This control system requires eleven (11) wires from the LV10 J-Box to the RPD10 remote panel
located in the kitchen.
8.0"
14.0"
IN PANEL BACK.
HOLES LOCATED
PANEL MOUNTING
5"
NORMAL
PREFILTER
CLOGGED
BAG FILTER
CLOGGED
FILTER
OVERIDE
FIRE
BOX FILTER
CLOGGED
REMOVED
FILTER
WARNING
KES
ON/OFF
RPD10 Remote Panel
Figure 14