Unit installation

_____________________________________________________________________________
Spring Air System Enviro Engineering Manual 01/0313
13
Typical Remote Wiring for Dry Hood
Figure 15
RPD10A Remote Annunciation Panel for automatic operation
Used in conjunction with a Dry Hood (Dry Extractor or Filter Hood)
The KES RPD10A remote control panel provides 24-hour/7 day operation and activates unit shut
down upon any of the conditions listed below.
1.Operation of the KES-ISH with dirty or clogged pre-filters, bag filters, or box filters.
2.Operation of the KES-ISH with the bag for box filter removed.
3.Low air volume through the KES-ISH.
4.A fire in the KES-ISH inlet
The RPD10A remote panel functions the
same as the standard RPD10 except the
microprocessor has the additional capability
of setting on/off operation three times a day
and 7 days per week.
ENVIRO FILTER UNIT
KES20-18-ISH
KESF20-18-IH
IN ACCORDANCE WITH THE NFPA-96 ALL WELDED
EXHA UST DUCTWORK FROM HOODS TO K ES UNIT TO B E
EXHAUST DISCHARGE DUCTWORK FROM THE KES UNIT
TO BE PER LOCAL AUTHORITIES HAVING JURISDICTION
DISC HA RGED
TO ATMOSPHERE
1840 CFM
19
LIQUID TIGHT CONSTRUCTION.
ENVIRO FAN UNIT
18
15
6
4
SLAB
MODEL DD-B-F-10.0/3.92
DRY GREASE EXTRACTOR
14
13
20
CONFORM TO ALL LOCAL CODES
FIEL D PIPING AND WIRING TO
REQUIREMENTS.
FINISHED CEILING
- 18 in. (457.2 mm) TO COMBUSTIBLE MA TERIAL
- 3 in. (76.2 mm) TO LIMITED-COMBUSTIBLE MATERIAL
- 0 in. (0 mm) TO NON-COMBUSTIBLE MATERIAL.
HOODS, GREASE EXTRACTORS, AND DUCTS
ALL WALLS SHOWN ARE ASSUMED TO BE
SHALL HAVE AT LEAST:
NON-COMBUSTIBLE.
CONTROLLER
RPD10
APPLIANCES
FINISHED FLOOR