Unit installation

_____________________________________________________________________________
Spring Air System Enviro Engineering Manual 01/0317
17
Engineering Data
Project Name: - Sample
Item Number: - EF-1
Model Number: - KES30-30-I-H
Arrangement: - indoor / horizontal
Unit Weight: - 1100 lbs.
Exhaust Volume: - 3000 CFM
External Static Pressure: - 1.75" W.C.
Brake Horsepower: - 4.66 Hp
Fan Speed: - 2766 rpm
Exhaust Fan Motor: - 5.00 Hp
Hi Voltage - FLA: - 208V/3/60 - 15.6 AMPS.
Low Voltage: - 120V/1/60 - 10 AMPS.
Remote Panel: - model RPW10
Hoods Connected:
Item # Model# Section#
H-1 CD-B-10/4 1
Sample KES Enviro Filter Selection Printout from Spring Air Program
Chart No. 4
Once again remember the Spring Air Systems sales representatives have a KES Enviro selection
program. Contact your local representative and a selection can be made in minutes.
SAMPLE SPECIFICATION
Kitchen Enviro Filter Unit Specification
The commercial kitchen enviro filter box shall be a SPRING AIR SYSTEMS Inc. model no.
KES___-___-I-H-S, indoor/outdoor design, horizontal/vertical arrangement, assembled, wired and
tested prior to shipment with exhaust capacity of ______ CFM at _____" W.C. internal static
pressure. The KES filter box shall be listed by Underwriters Laboratories Inc., Underwriters
Laboratories of Canada and installed in accordance to the NFPA-96, the national building code,
and local authorities having jurisdiction.
Unit Casing:
The filter box section casing shall be double wall, sandwich insulation construction. The inner
wall shall be a minimum 16-gauge liquid tight and the outer wall shall be a minimum 18-gauge
construction. The sandwiched insulation shall be 1.5" fiberglass. The unit casing shall be
suitably reinforced to ensure rigidity. The filter section shall have a fire damper at the exhaust
exit. Double walled, insulated, hinged access doors with cam lock fasteners shall be provided for
entry to the filter sections. A fire damper shall be located in the filter section outlet.
Filter Section:
The KES unit shall include three stages of particulate filtration. The first stage shall be a 2"
pleated UL/ULC Class 2 filter, rated at 30% ASHRAE 52-76. The second stage shall be a 22" bag
filter, UL/ULC Class 2, rated at 90% ASHRAE 52-76. The third stage shall be a 12" box filter,
UL/ULC Class 2, rated at 95% DOP or 99% ASHRAE 52-76.
Controls: Indoor Unit
The KES-ISH filter unit shall have a NEMA-1 LV10 J-Box, pressure switches, and a fire stat
located on the unit. The LV10 J-BOX shall be interconnected to the KESF fan unit and a RPD10,
or RPD10A or RPW10 remote panel.