Controls: Outdoor Unit
The LV10 J-Box, and pressure switches shall be located in a weatherproof enclosure with the
motor starter and overload on the KESF fan unit. When the odor spray option is selected this
enclosure will have a 300-watt baseboard heater and thermostat in cold climates. The unit shall
include a firestat. The LV10 J-BOX shall be interconnected to a RPD10, RPD10A or RPW10
remote panel.
Remote Station Option:
RPD-10: Dry Hoods Manual Operation: For model FD/FN/DD/DN
The remote control station shall include a microprocessor for control and operation of the
KES unit. There shall be pilot lights for NORMAL operation, FIRE, BOX FILTER
CLOGGED, BAG FILTER CLOGGED, PREFILTER CLOGGED, FILTER REMOVED, and
WARNING and unit ON/OFF and SERVICE OVERIDE switches. When the odor spray
option is selected the spray cycle and spray times are set at this panel.
RPD-10A: Dry Hoods Manual Automatic: For model FD/FN/DD/DN
The remote control shall include a microprocessor for control and 24-hour/7 day
automatic operation of the KES unit. There shall be pilot lights for NORMAL operation,
FIRE, BOX FILTER CLOGGED, BAG FILTER CLOGGED, PREFILTER CLOGGED,
FILTER REMOVED, and WARNING and unit ON/OFF and SERVICE OVERIDE
switches. The KES automatic daily and weekly on/off times are set at this panel. When
the odor spray option is selected the spray cycle and spray are set at this panel.
RPW-10: Wash hoods model CD/HD/CF/HF/CT/HT
The remote control shall include a microprocessor for control and operation of the KES
unit. There shall be pilot lights for NORMAL operation, FIRE, BOX FILTER CLOGGED,
BAG FILTER CLOGGED, PREFILTER CLOGGED, FILTER REMOVED, and WARNING
and a SERVICE OVERIDE switch. The KES on/off operation is controlled at the water
wash panel. When the odor spray option is selected the spray cycle and spray are set at
this panel.
Mechanical Services:
All exhaust ductwork from the kitchen hood to the KES inlet shall be supplied and installed in
accordance to the NFPA-96. The KES exhaust discharge ductwork shall conform to local
building code requirements.
Kitchen Enviro Fan Unit Specification:
The commercial kitchen enviro fan unit shall be a SPRING AIR SYSTEMS Inc. model no.
KESF___, indoor/outdoor design, horizontal/vertical arrangement, assembled, wired and tested
prior to shipment with exhaust capacity of ______ CFM at _____" W.C. total static pressure. The
KES fan unit shall be listed by Underwriters Laboratories Inc., Underwriters Laboratories of
Canada and installed in accordance to the NFPA-96, the national building codes, and local
authorities having jurisdiction.
Unit Casing:
The exhaust fan motor and drive section shall be single wall construction with minimum 16 gauge
wall and 1" sound attenuation insulation. The exhaust fan section shall be internally/externally
spring isolated.