Unit installation
_____________________________________________________________________________
Spring Air System Enviro Engineering Manual 01/032
2
The KES unit is installed to clean the exhaust air of grease and odor. The UL/ULC listing allows
the exhaust to be discharged at low levels.
In other words the exhaust ductwork may be discharged through side exterior walls below the
roof level. These exceptions to the standard NFPA-96 code are possible with a combination high
efficiency filtration system and a unique electrical and mechanical safety circuit.
The KES Enviro unit is available in sizes ranging from
1,000 to 40,000 CFM
(475 to 19,000 l/s), horizontal or vertical arrangement, (vertical units are available up to 8,000
CFM (3,800 l/s) indoor or outdoor design, and for use with dry hoods or water wash ventilators. A
few typical applications are shown in Figure No. 1.
PRINCIPLE OF OPERATION
The grease-laden air rises from the cooking equipment into the UL/ULC, commercial kitchen
exhaust hood. The exhaust hood will remove some of the airborne grease, lint and dirt
particulate. Typically most micron and submicron particle escape into the ductwork. The exhaust
air is then ducted directly to the inlet of the KES Enviro Filter Unit. This exhaust duct from the
commercial kitchen exhaust hood to the inlet of the KES Enviro must be installed in strict
accordance with the NFPA-96 code.
KES-ISH Plan View of Filter Box Schematic
Figure 2
EXHAUST
OUTLET
EXHAUST
INLET
PRESSURE SWITCHES
CHANNEL BASE
LV10 CONTROLLER
12" BOX FILTERS
2" PREFILTERS
21" BAG FILTERS
16 GA. ALL WELDED INTERIOR
FUSIBLE LINK FIRE DAMPER
1.5" TWO WALL INSULATED PANELS