Owner`s manual
Rain cap - ensure cap is at 
least 2 feet (610mm) above 
the roof at the lowest point
Storm collar
Roof flashing
Roof rafter
Fire stop with 
Support Collar
Ceiling joist
Vertical vent pipe
Clean out tee with 
Pipe adapter
NOTE:
All vent sections must maintain 3" 
(76 mm) clearances to combustibles. 
Unless otherwise specified by the 
vent manufacturer’s instructions.
15
inSiDe veRticaL inStaLLationS - fReeStanDing:
1. Choose a stove location that is ideal.  See the section “installation - deciding where to locate your pellet 
appliance.” 
Figure 17: Inside Vertical Installation. 
Recommended vent size for vertical installation:
Under 15ft:  3” Vent
Over 15ft:  4” Vent
2. Place  the  unit  on  the 
hearth  pad  (if  installed  on 
a  carpeted  surface)  and 
space the unit in  a manner 
so  when  the  pellet  vent  is 
installed vertically, it will be 
3” (76  mm) away from a 
combustible wall.
3. Locate  the  center  of  the 
fresh air intake pipe on the 
unit. Match that center with 
the same  point on the  wall 
and cut a hole about 2” (51 
mm) in diameter.
4. Install  the  fresh  air  intake 
pipe.
5. Install  the  tee  with  clean 
out.
6. 
Install  the  pellet  vent 
upward  from  there.    When 
you reach the ceiling, make 
sure  that  the  vent  goes 
through the ceiling fire stop.  
Maintain  a  3”  (76  mm) 
distance  to  combustibles 
and  keep  attic  insulation 
away from the vent pipe. 
Maintain  an  effective  vapor 
barrier.
7.  Finally,  extend  the  pellet 
vent to go through the roof 
flashing.
8. Ensure  that  the  rain  cap 
is  approximately  24”  (610 
mm) above the roof.