Owner`s manual
17
1. Lock  fireplace  damper  in  the  open 
position.
2. Install  a  positive  flue  connector  at  the 
fireplace dampers.
3. Connect a clean-out tee or a 90° elbow to 
the exhaust pipe.
4. Install flexible stainless steel liner or listed 
pellet vent to the top of the chimney.
Recommended  vent  size  for  vertical 
installation:
Under 15ft:  3” Vent
Over 15ft:  4” Vent
heaRth mount inStaLLation - fReeStanDing:
Figure 19: Hearth Mount - Side View. 
Figure 20: Hearth Mount - Over View. 
Floor
Protection
Combustible FloorMasonry Fireplace
Min 9" 
Mantel
Minimum 8" (20 cm) 
from top of stove
NOTE: Hopper lid will not open fully
  with less than 13.5”.
Damper Removed
or Fastened Open
Clean-out tee
Fresh-air intake should 
come from chimney. If 
holes already exist 
fresh-air intake can be 
taken through back of 
the fireplace or through 
the ash dump.
Rain cap
Storm collar
Seal plate 
(cover plate)
Existing masonry 
flue
Vent pipe (single 
wall stainless flex 
pipe or solid PL 
vent)
Fireplace damper 
location
Clean out tee
Existing fireplace
Flexible vent 
connector (use this 
5' [1520 mm] section 
of pipe to vent past 
fireplace damper or 
small shelf)