Initial Installation
QUALIFIED INSTALLERS ONLY
The framing boards may touch the top, side and back standoffs, but no insulation or other material
can be placed between the frame and the standoffs.
The gas line, inch NPT, can be brought to either the right side, the left side, or the bottom of
the replace. If this set up is inconvenient, the electrical wire and the gas line conguration can be
reversed.
The location should be chosen so the replace must be at least 36 inches (91.4 cm) from drapes, doors
and other combustibles. The framed opening should also be a minimum of 3.5 inches (8.9 cm) from the
nearest perpendicular wall (sidewall to the edge of the opening).
The HAVEN is designed so it can be installed at oor level without a required hearth.
CORNER INSTALLATION:
RAISED FIREPLACES AND HEARTHS:
Even though the Haven can be installed at oor level without a hearth, there are a few options with raised
replaces: raised with a oor level hearth (Figure 17), raised with a raised hearth (Figure 18), or raised
with no hearth (Figure 19). If the replace is raised, it cannot be placed within 18 inches (45.7cm) of the
ceiling. When installing a raised replace, it is imperative that the support stand is strong enough to hold
the weight of the replace (up to 140lb [63.5Kg]) and venting.
Figure 16. Dimensions for a corner installation.
2" x 6"
Stud
1
/2" (13mm)
Front Facing
18
15
/16"
(481mm)
30
5
/16"
(770mm)
21
7
/16"
(545mm)
6
3
/8"
(162mm)
The dimensions for installing a
replace in the corner of a room
are given in Figures 16. Refer
to “INITIAL INSTALLATION - VENT
CONFIGURATIONS AND RESTRICTOR
SETTINGS” for allowable pipe
lengths.
Do not interfere with the
structural integrity of the walls.
14