User manual

Figure 32. Vent Framing Through Wall/Ceiling.
Figure 31. Vent Pipe Clearances.
2" (51mm)
7
11
/16" (195mm)
39"
(991mm)
Framing
Joists/Studs
10”
10”
Initial Installation
QUALIFIED INSTALLERS ONLY
VENTING:
This replace has been tested and certied for use with SIMPSON DURAVENT DIRECT VENT TYPE “GS”
PIPE FOR GAS STOVES, SECURITY CHIMNEY’S SECURE VENT DIRECT VENT SYSTEM kits, AMERICAN
METAL PRODUCTS AMERIVENT DIRECT and DIRECT-TEMP SELKIRK METALBESTOS.
A 1” (25 mm) clearance to combustibles must be maintained around any vertical vent pipe. Around a
horizontal vent pipe, the clearance to combustibles should be 2” (51 mm) above and 1” (38 mm) on
the sides and bottom. When combustible materials are directly above a 90° elbow, 3 inches (7.6 cm) of
clearance are necessary (see Figure 31).
Table 6. Vent Pipe Minimum Clearances.
Vertical Pipe to
the Side Walls
Horizontal Pipe to
the Sides & Bottom
Above an Elbow
Above the Unit
Above an Elbow
Not Above the Unit
Above Horizontal
Vent Pipe
Wall Frame 8”
(203mm) or less
Hard
Pipe
1”
(25.4 mm)
1”
(38.1 mm)
7
11
/16
(195mm)
3”
(76.2 mm)
2”
(51 mm)
10”x10”
(25x25cm)
Flex
Pipe
1”
(25.4 mm)
1”
(38.1 mm)
7
11
/16
(195mm)
3 ”
(86 mm)
3 ”
(86 mm)
10”x10”
(25x25cm)
A 10” (254 mm) x 10” (254 mm) frame (see Figure 32) will assure the proper support and spacing for
the vent pipe as it passes through the wall. Installations in Canada require that a wall thimble be used
for passing through walls and ceilings. All sealing and vapour barriers must comply with local building
codes.
When planning an installation, it is necessary to select the proper length
of vent pipe for the particular requirements. The conguration of the
venting pipes depends on the locations of walls, ceilings and studs.
However, the pipes cannot be of arbitrary length and arrangement.
Because the length of the vertical and horizontal sections dramatically
affects the burning efciency of the replace, certain guidelines have
been set in INITIAL INSTALLATION - VENT CONFIGURATIONS AND RESTRICTOR
SETTINGS.
Venting terminals can not be recessed into a wall or siding.
WARNING: This gas appliance must not be connected to a
chimney ue serving a separate solid-burning appliances.
22